Parameter Value
Extended ambient temperature (XC version) >60 °C on request
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
Parameter Value
Bus connection 2 x RJ45
Switch Integrated
Technology Hilscher NETX 100
Transfer rate 10/100 Mbit/s (full-duplex)
Transfer method According to Ethernet II, IEEE 802.3
Ethernet 100 base-TX, internal switch, 2x RJ45 socket
Expandability Max. 10 S500 I/O modules
Adjusting elements 2 rotary switches for generation of an explicit
name
Supported protocols RTC - real time cyclic protocol, class 1 *)
RTA - real time acyclic protocol
DCP - discovery and configuration protocol
CL-RPC - connectionless remote procedure
Call
LLDP - link layer discovery protocol
MRP - MRP Client
Acyclic services PNIO read / write sequence (max. 1024 bytes
per telegram)
Process-Alarm service
Supported alarm types Process Alarm, Diagnostic Alarm, Return of
SubModule, Plug Alarm, Pull Alarm
Min. bus cycle 1 ms
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31 3ADR010278, 3, en_US 831