162
13.3.2 Configuration of connection PLC with GP/PLC type window   
In order to transmit written data in GP editor to PLC, configure group, type, communication type of 
connected PLC.   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Configuration of PLC type connected to GP   
①GP type 
•
 Designate current using GP model type. 
②
•
 Designate current connected PLC group of CH1 
③CH1 type 
•
 Configure PLC type for connected CH1 group.   
④GP connection device 
• Configure the lead word address of GP to communicate with CH1. 
• If data link is required between 
GP and CH1, it is only available when 
⑤
⑤
device 
•  If data interlock is required between GP and CH1, configure CH1 
address to communicate with GP.   
• Checking a box, the line is activated, configure start device, bit/word, 
numbers, read/write of CH1 to communicate with GP. 
⑥
•
 Designate current connected PLC group of CH2. 
⑦CH2 type 
•
 Configure PLC type for selected CH2 group.   
⑧
•
 Configure the lead word address of GP to communicate with CH2.   
⑨Station and connection 
device 
• Configure station and the lead address of PLC2 to communicate with 
G P.    
• Check the station to use, a proper button is activated and start device 
of CH1 to communicate with GP, bit/word, numbers, read/write are 
configured displaying same type of window with ⑤when selecting a 
⑩Connection diagram 
• Display configuration of device link as a table between configured GP-
① 
② 
③ 
④ 
⑤ 
⑥ 
⑦ 
⑧ 
⑨ 
⑩