162
13.3.2 Configuration of connection PLC with GP/PLC type window
In order to transmit written data in GP editor to PLC, configure group, type, communication type of
connected PLC.
Configuration of PLC type connected to GP
â‘ GP type
•
Designate current using GP model type.
â‘¡
•
Designate current connected PLC group of CH1
â‘¢CH1 type
•
Configure PLC type for connected CH1 group.
â‘£GP connection device
• Configure the lead word address of GP to communicate with CH1.
• If data link is required between
GP and CH1, it is only available when
⑤
⑤
device
• If data interlock is required between GP and CH1, configure CH1
address to communicate with GP.
• Checking a box, the line is activated, configure start device, bit/word,
numbers, read/write of CH1 to communicate with GP.
â‘¥
•
Designate current connected PLC group of CH2.
⑦CH2 type
•
Configure PLC type for selected CH2 group.
â‘§
•
Configure the lead word address of GP to communicate with CH2.
⑨Station and connection
device
• Configure station and the lead address of PLC2 to communicate with
G P.
• Check the station to use, a proper button is activated and start device
of CH1 to communicate with GP, bit/word, numbers, read/write are
configured displaying same type of window with ⑤when selecting a
â‘©Connection diagram
• Display configuration of device link as a table between configured GP-
â‘
â‘¡
â‘¢
â‘£
⑤
â‘¥
⑦
â‘§
⑨
â‘©