20.PROFINET COMMUNICATION
When Reset To Factory is used with a driver on which MR-D30 functional safety
unit is mounted, [AL. 7A.3 Parameter combination error (safety observation
function)] or [AL. 79.4 Driver error] will occur. Cycle the power of the driver.
With Reset To Factory, you can reset the parameters of the device to the factory setting. Since the operation
methods of Reset To Factory differs depending on configuration software, refer to the manuals for the
configuration software.
This function resets the communication parameters to the factory setting. (Note 1)
Reset equivalent to power off/on will be executed.
The station name will be "" (null character).
IP address will be "0.0.0.0".
This function resets the communication parameters, driver parameters and the point table to the factory setting.
Reset equivalent to power off/on will be executed.
The station name will be "" (null character).
IP address will be "0.0.0.0".
Parameter default will be executed. (Note 2)
Point table default will be executed.
Parameter default of MR-D30 functional safety unit will be executed.
With Reset To Factory, the values are written to EEP-ROM even when in Reset Option 2. Note that the number of write
times to the EEP-ROM is limited to 100,000. If the total number of write times exceeds 100,000, the driver may
malfunction when the EEP-ROM reaches the end of its useful life.
The following parameters will be reset;
Basic setting parameters [Pr. PA_ _ ]
Gain/filter setting parameters [Pr. PB_ _ ]
Extension setting parameters [Pr. PC_ _ ] (except [Pr. PC11] and [Pr. PC12])
I/O setting parameters [Pr. PD_ _ ]
Extension setting 2 parameters [Pr. PE_ _ ]
Extension setting 3 parameters [Pr. PF_ _ ]
Linear servo motor/DD motor setting parameters [Pr. PL_ _ ]
Positioning control parameters [Pr. PT_ _]
Network setting parameters [Pr. PN_ _]