13. USING STO FUNCTION
13 - 10
13.3.3 External I/O signal connection example using an external safety relay unit
POINT
This connection is for the source interface. For the other I/O signals, refer to the
connection examples in section 3.2.
This connection example complies with the requirement of ISO/EN ISO 13849-1 category 3 PL d.
KM1
KM1
KM1
EMGS4
S3
Safety relay module
MELSEC
(QS90SR2S)
Fuse
24 V
0 V
S2
S1 or
EMG
(Note)
EMG
K3
Control
circuit
Power
supply
KM1
S1: STO shut-off sw itch (STO switch)
S2: Start switch (STO release switch)
S3: On sw itch
S4: Off switch
KM1: Magnetic contactor
K3: Safety relay
EMG: Emergency stop switch
+24 V XS0 XS1 Z00 Z10 Z20
X0
COM0
24G
X1
COM1
Z01 Z11 Z21
K3
CN8
CN3
20
EM1
or
EM2
Control circuit
Servo amplifier
STO1
TOFB1
TOFCOM
TOFB2
STO2
STOCOM
M
Servo motor
Note.
To enable the STO function of the driver by using "Emergency switching off", change S1 to EMG. The stop category at this time
is "0". If STO is turned off while the servo motor is rotating, [AL. 63 STO timing error] will occur.
Driver

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks LECSN-T Series and is the answer not in the manual?

SMC Networks LECSN-T Series Specifications

General IconGeneral
BrandSMC Networks
ModelLECSN-T Series
CategoryController
LanguageEnglish

Related product manuals