Loading...
Parameter Value
Connection of the supply voltage 24 V
DC at the terminal base of the processor
module
Removable 5-pin terminal block spring type
Max. current consumption from 24 V DC
TB5600: 0.25 A
1
)
TB5610: 0.35 A
1
)
TB5620: 0.4 A
1
)
TB5640: 0.6 A
1
)
TB5660: 0.8 A
1
)
Melting integral of a fuse at 24 V DC
Min. 1 A²s
2
)
Peak inrush current from 24 V DC
55 A
2
)
Number of slots for processor modules 1 (on all terminal bases)
Processor module interfaces at TB56xx I/O bus, ETH1, ETH2, CAN, COM1
Net weight (terminal base without pro-
cessor module)
TB5600: 155 g
TB5610: 180 g
TB5620: 210 g
TB5640: 260 g
TB5660: 310 g
Mounting position Horizontal or vertical
1
) Including processor modules, communication modules and communication interface modules
2
) The inrush current and the melting integral depends on the internal power supply of the
processor module and the number and type of communication modules and I/O modules
connected to the I/O bus.
Table 3: Combination of TB56xx-2ETH(-XC) and PM56xx(-XC)
Processor module PM5630 PM5650 PM5670 PM5675
TB5600-2ETH 0 slot 0 slot 0 slot 0 slot
TB5610-2ETH 1 slot 1 slot 1 slot 1 slot
TB5620-2ETH 2 slots 2 slots 2 slots 2 slots
TB5640-2ETH - 4 slots 4 slots 4 slots
TB5660-2ETH - -
6 slots
1
) 6 slots
1
)
Remarks:
The slots can be used for connecting communication modules or AC500-S modules. Note that
only one AC500-S module can be connected at one terminal base.
1
) PM567x must have an index C0.
Device specifications
Terminal bases (AC500 standard) > TB56xx for AC500 V3 products
2022/01/313ADR010278, 3, en_US12