EasyManua.ls Logo

ABB AC500 V3 - Page 128

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WARNING!
Electric shock due to negligent behavior during hot swapping!
To avoid electric shock
make sure the following conditions apply:
Digital outputs are not under load.
Input/output voltages above safety extra low voltage/
protective extra low voltage (SELV/PELV) are switched off.
Modules are fully interlocked with the terminal unit with both snap-fits
engaged before switching on loads or input/output voltage.
Never touch exposed contacts (dangerous voltages).
Stay away from electrical contacts to avoid arc discharge.
Do not operate a mechanical installation improperly.
NOTICE!
Risk of damage to I/O modules!
Hot swapping is only allowed for I/O modules.
Processor modules and communication interface modules must not be removed
or inserted during operation.
H = Hot swap
Hot swap
System requirements for hot swapping of I/O modules:
Types of terminal units that support hot swapping of I/O modules have the
appendix TU5xx-H.
I/O modules as of index F0.
The following I/O bus masters support hot swapping of attached I/O modules:
Communication interface modules CI5xx as of index F0.
Processor modules PM56xx-2ETH with firmware version as of V3.2.0.
Hot swap is not supported by AC500-eCo V3 CPU!
Device specifications
Terminal units (AC500 standard) > TU515, TU516, TU541 and TU542 for I/O modules
2022/01/313ADR010278, 3, en_US128

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals