EasyManua.ls Logo

ABB AC500 V3 - Page 260

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NOTICE!
Risk of damaging the PLC modules!
The PLC modules can be damaged by overload.
Make sure that the total current of each output common terminal (R0..3 and
R4..7) does not exceed 8 A.
Never connect total currents > 8 A per group.
If the group fuse protection is not sufficient, then individual fuse protection of the
outputs should be used.
The module provides several diagnosis functions (see Diagnosis
Ä
Chapter 1.6.1.1.13.6 “Diag-
nosis” on page 264).
The digital inputs can be used as source inputs or as sink inputs.
NOTICE!
Risk of malfunctions in the plant!
A ground fault, e. g. caused by a damaged cable insulation, can bridge switches
accidentally.
Use sink inputs when possible or make sure that, in case of error, there will be
no risks to persons or plant.
The following figures show the connection of the inputs to the digital input/output module
DX571:
1
2
C0..7
I0
4
I2
3
I1
5
I3
6
7
I5
8
I6
9
I7
I4
24 V
DC/AC
+ / ~
– / ~
Fig. 16: Connection of inputs - sink inputs
Device specifications
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US260

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals