The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
Name Value Internal
value
Internal
value,
type
Default Min. Max. EDS Slot/
Index
Module ID Internal 1210
1
)
Word 1210
0x04BA
0 65535 0x0Y01
Ignore
module
2
)
No
Yes
0
1
Byte No
0x00
    Not for
FBP
Parameter
length
Internal 5 Byte 5-CPU
4-FBP
0 255 0x0Y02
Check
supply
Off
On
0
1
Byte On
0x01
0 1 0x0Y03
Input
delay
0.1 ms
1 ms
8 ms
32 ms
0
1
2
3
Byte 8 ms
0x02
0 3 0x0Y04
Fast
Counter
4
)
0
:
10
3
)
0
:
10
Byte Mode 0
0x00
    Not for
FBP
Behaviour
of outputs
at com-
munica-
tion errors
Off
Last value
Substitute
value
0
1+(n*5)
2+(n*5),
n £ 2
Byte Off
0x00
0 2 0x0Y05
Substitute
value at
outputs)
Bit 7 =
Output 7
Bit 0 =
Output 0
0...
255
0...
0xff
Byte 0
0x00
0 255 0x0Y06
Remarks:
1
)
With CS31 and addresses smaller than 70 and FBP, the value is increased
by 1
2
)
Not with FBP
3
)
For a description of the counter operating modes, please refer to the 'Fast
Counter' section 
Ä
 Chapter 1.6.1.2.9 “Fast counter” on page 349
4
)
With FBP and without the parameter Fast Counter
 
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US334