E1..E4 d1 d2 d3 d4 Identi-
fier
000..063
AC500
display
<− Display in
Class Comp Dev Mod Ch Err PS501
PLC
Browser
Byte 4
Bit 6..7
- Byte 1 Byte 2 Byte 3 Byte 4
Bit 0..5
CANope
n diag-
nosis
block
Class Inter-
face
Device Module Channel Error
identi-
fier
Error message Remedy
1
)
2
)
3
)
4
)
3 - 31 31 31 11 Process voltage UP
too low
Check
process
supply
voltage
3 - 31 31 31 45 Process voltage UP
gone
Check
process
supply
voltage
3 - 31/1...10 31 31 17 No communication
with I/O module
Replace
I/O
module
3 - 1...10 31 31 32 Wrong I/O module
type on socket
Replace
I/O
module /
check
configu-
ration
4 - 1...10 31 31 31 At least one
module does not
support failsafe
function
Check
modules
and
parame-
terization
4 - 31 31 31 45 Process voltage
UP3 too low
Check
process
voltage
4 - 31 31 31 46 Voltage feedback
on activated digital
outputs
4
)
Check
terminals
4 - 31/1...10 31 31 34 No response during
initialization of the
I/O module
Replace
I/O
module
4 - 31 31 31 11 Process voltage
UP3 too low
Check
process
supply
voltage
4 - 31 31 31 45 Process voltage
UP3 gone
Check
process
supply
voltage