Name Value Internal value Internal value,
type
Default
Output 0, Substi-
tute value
Table Substitute
value
Ä
Table 160 “Su
bstitute value”
on page 753
Table Substitute
value
Ä
Table 160 “Su
bstitute value”
on page 753
WORD 0
Output 1,
Channel configu-
ration
Table Operating
modes of the
analog outputs
Ä
Table 158 “Ch
annel configura-
tion”
on page 753
Table Operating
modes of the
analog outputs
Ä
Table 158 “Ch
annel configura-
tion”
on page 753
BYTE 0
Output 1, Check
channel
Table Channel
monitoring
Ä
Table 159 “Ch
annel monitoring”
on page 753
Table Channel
monitoring
Ä
Table 159 “Ch
annel monitoring”
on page 753
BYTE 0
Output 1, Substi-
tute value
Table Substitute
value
Ä
Table 160 “Su
bstitute value”
on page 753
Table Substitute
value
Ä
Table 160 “Su
bstitute value”
on page 753
WORD 0
Table 158: Channel configuration
Internal value Operating modes of the analog outputs, individually configu-
rable
0 (default) Not used
128 -10 V...+10 V
129 0...20 mA
130 4...20 mA
Table 159: Channel monitoring
Internal value Check channel
0 Plausib(ility), cut wire, short circuit
3 None
Table 160: Substitute value
Intended behavior of output
channel when the control
system stops
Required setting of the
module parameter "Behav-
iour of outputs in case of a
communication error"
Required setting of the
channel parameter "Substi-
tute value"
Output OFF Off 0
Last value infinite Last value 0
Last value for 5 s and then
turn off
Last value 5 sec 0
Last value for 10 s and then
turn off
Last value 10 sec 0
Substitute value infinite Substitute value Depending on configuration
Device specifications
Communication interface modules (S500) > Modbus
2022/01/31 3ADR010278, 3, en_US 753