Name Value Internal value Internal value,
type
Default
Input delay 8 ms 8 ms BYTE 8 ms
Fast counter 0
:
10
3
)
0
:
10
BYTE 0
Detect short cir-
cuit at outputs
On 1 BYTE On
Behavior digital
outputs at comm.
error
Off 0 BYTE Off
Substitute value
digital outputs
0 0..255 BYTE 0
Overvoltage
behavior on
output
Off 0 BYTE Off
Behavior analog
outputs atcomm.
error
Off 0 BYTE Off
I/O-Bus reset Off 0 BYTE Off
On 1 BYTE Off
Remarks:
1
)
With a faulty ID, the modules reports a "parameter error" and does not perform
cyclic process data transmission.
2
)
As for device index C0 the parameter is no longer evaluated.
3
)
Counter operating modes, see description of the Fast counter
Ä
Chapter
1.6.1.2.9 “Fast counter” on page 349.
Table 166: Error LED / Failsafe function
Setting Description
On Error LED (S-ERR) lights up at errors of all
error classes, Failsafe-mode off
Off by E4 Error LED (S-ERR) lights up at errors of error
classes E1, E2 and E3, Failsafe-mode off
Off by E3 Error LED (S-ERR) lights up at errors of error
classes E1 and E2, Failsafe-mode off
On +Failsafe Error LED (S-ERR) lights up at errors of all
error classes, Failsafe-mode on *)
Off by E4 + Failsafe Error LED (S-ERR) lights up at errors of error
classes E1, E2 and E3, Failsafe-mode on *)
Off by E3 + Failsafe Error LED (S-ERR) lights up at errors of error
classes E1 and E2, Failsafe-mode on *)
*) The parameters Behaviour AO at comm. error and Behaviour DO at comm. error are only
analyzed if the Failsafe-mode is ON.
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/313ADR010278, 3, en_US816