NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
– Make sure that all voltage sources (supply voltage and process supply
voltage) are switched off before you begin with operations on the system.
– Never connect any voltages or signals to reserved terminals (marked with
---). Reserved terminals may carry internal voltages.
When replacing a processor module, it is recommended to mark each wire
connected to the onboard I/O terminal block before disconnecting it. This should
make sure that the wires can be reconnected in the same order.
The connection is carried out by using removable 12-pin and 13-pin terminal blocks.
Table 10: Assignment of the terminals for PM5012-T-ETH:
Terminal Signal Description
1 COM 0..5 Input common for digital input signals I0 to I5
2 I0 Digital input signal I0 (5 kHz)
3 I1 Digital input signal I1 (5 kHz)
4 I2 Digital input signal I2 (5 kHz)
5 I3 Digital input signal I3 (5 kHz)
6 I4 Digital input signal I4 (5 kHz)
7 I5 Digital input signal I5 (5 kHz)
8 O0 Digital output signal O0 (5 kHz)
9 O1 Digital output signal O1 (5 kHz)
10 O2 Digital output signal O2 (5 kHz)
11 O3 Digital output signal O3 (5 kHz)
12 UP Process supply voltage UP +24 V DC
13 ZP Process supply voltage ZP 0 V DC
Table 11: Assignment of the terminals for PM5012-R-ETH:
Terminal Signal Description
1 COM 0..5 Input common for digital input signals I0 to I5
2 I0 Digital input signal I0 (5 kHz)
3 I1 Digital input signal I1 (5 kHz)
4 I2 Digital input signal I2 (5 kHz)
5 I3 Digital input signal I3 (5 kHz)
6 I4 Digital input signal I4 (5 kHz)
7 I5 Digital input signal I5 (5 kHz)
8 NO0 Normally-open relay contact of the output NO0
9 NO1 Normally-open relay contact of the output NO1
10 R0..1 Output common for signals NO0 to NO1
Processor modules > AC500-eCo
2022/01/313ADR010278, 3, en_US28