Terminal Signal Description
24 UP Process supply voltage UP +24 V DC
25 ZP Process supply voltage ZP 0 V DC
Table 13: Assignment of the terminals for PM5032-R-ETH and PM5052-R-ETH:
Terminal Signal Description
1 COM 0..11 Input common for digital input signals I0 to I11
2 I0 Digital input signal I0 (max. 5 kHz)
3 I1 Digital input signal I1 (max. 5 kHz)
4 I2 Digital input signal I2 (max. 5 kHz)
5 I3 Digital input signal I3 (max. 5 kHz)
6 I4 Digital input signal I4
Forward counter (max. 100 kHz), Encoder (max. 200
kHz)
7 I5 Digital input signal I5
Forward counter (max. 100 kHz), Encoder (max. 200
kHz)
8 I6 Digital input signal I6
Forward counter (max. 100 kHz), Encoder (max. 200
kHz)
9 I7 Digital input signal I7
Forward counter (max. 100 kHz), Encoder (max. 200
kHz)
10 I8 Digital input signal I8
11 I9 Digital input signal I9
12 I10 Digital input signal I10
13 I11 Digital input signal I11
14 NO0 Normally-open relay contact of the output NO0
15 NO1 Normally-open relay contact of the output NO1
16 NO2 Normally-open relay contact of the output NO2
17 R0..2 Output common for signals NO0 to NO2
18 NO3 Normally-open relay contact of the output NO3
19 NO4 Normally-open relay contact of the output NO4
20 NO5 Normally-open relay contact of the output NO5
21 R3..5 Output common for signals NO3 to NO5
22 C12 Digital input/output signal configurable C12
PWM (max. 100 kHz), PTO (max. 200 kHz)
23 C13 Digital input/output signal configurable C13
PWM (max. 100 kHz), PTO (max. 200 kHz)
24 UP Process supply voltage UP +24 V DC
25 ZP Process supply voltage ZP 0 V DC
Device specifications
Processor modules > AC500-eCo