Table 81: Input channel (8x)
No. Name Internal value, type Default
1 Channel configuration
see table
2
)
Byte 0
0x00 see table
2
)
2 Channel monitoring
see table
3
)
Byte 0
0x00 see table
3
)
Table 82: Channel configuration
2
)
Internal value Operating modes of the analog inputs, individually configurable
0 Unused (default)
1 Analog input 0 V...10 V
2 Digital input
3 Analog input 0 mA...20 mA
4 Analog input 4 mA...20 mA
5 Analog input -10 V...+10 V
8 Analog input Pt100, -50 °C...+400 °C (2-wire)
9 Analog input Pt100, -50 °C...+400 °C (3-wire), requires 2 channels *)
10 Analog input 0...10 V via differential inputs, requires 2 channels *)
11 Analog input -10 V...+10 V via differential inputs, requires 2 channels *)
14 Analog input Pt100, -50 °C...+70 °C (2-wire)
15 Analog input Pt100, -50 °C...+70 °C (3-wire), requires 2 channels *)
16 Analog input Pt1000, -50 °C...+400 °C (2-wire)
17 Analog input Pt1000, -50 °C...+400 °C (3-wire), requires 2 channels *)
18 Analog input Ni1000, -50 °C...+150 °C (2-wire)
19 Analog input Ni1000, -50 °C...+150 °C (3-wire), requires 2 channels *)
*) In the operating modes with 3-wire configuration or with differential inputs,
two adjacent analog inputs belong together (e.g. the channels 0 and 1). In
these cases, both channels are configured in the desired operating mode. The
lower address must be the even address (channel 0). The next higher address
must be the odd address (channel 1). The converted analog value is available
at the higher address (channel 1).
Table 83: Channel monitoring
3
)
Internal value Monitoring
0 Plausibility, open-circuit (broken wire) and short circuit
1 Open-circuit and short-circuit
2 Plausibility
3 No monitoring
I/O modules > Analog I/O modules