Table 84: Output channel 0 (1 channel)
No. Name Value Internal value Internal
value, type
Default
1 Channel con-
figuration
see table
4
) see table
4
)
Byte
see table
4
)
2 Channel mon-
itoring
see table
5
) see table
5
)
Byte
see table
5
)
3 Substitute
value
see table
6
)
0...65535 0...
0xffff
Word 0
Table 85: Output channels 1...7 (7x)
No. Name Internal value, type Default
1 Channel configura-
tion
see table
4
)
Byte
see table
4
)
2 Channel monitoring
see table
5
)
Byte
see table
5
)
Table 86: Channel configuration
4
)
Internal value Operating modes of the analog outputs, individually configurable
0 Unused (default)
128 Analog output -10 V...+10 V
129 Analog output 0 mA...20 mA (not with the channels 4...7)
130 Analog output 4 mA...20 mA (not with the channels 4...7)
Table 87: Channel monitoring
5
)
Internal value Monitoring
0 Plausibility, open circuit (broken wire) and short circuit (default)
1 Open-circuit (broken wire) and short-circuit
2 Plausibility
3 No monitoring
Table 88: Substitute value
6
)
Intended behavior of output
channel when the control
system stops
Required setting of the
module parameter "Behav-
iour of outputs in case of a
communication error"
Required setting of the
channel parameter "Substi-
tute value"
Output OFF Off 0
Last value Last value 0
Substitute value Off or last value 1...65535
Device specifications
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 423