No. Name Value Internal
value
Internal
value,
type
Default Min. Max. EDS
Slot/
Index
22 Channel
configu-
ration
Output
channel
3
See table
Ä
Table 101 “Chan
nel configuration
2
)”
on page 513
Byte Default
0x00
0 130 0x0Y15
23 Channel
moni-
toring
Output
channel
3
See table
Ä
Table 102 “Chan
nel monitoring
3
)”
on page 514
Byte Default
0x00
0 3 0x0Y16
1
) With CS31 and addresses less than 70 and FBP, the value is increased by 1
2
) Not with FBP
GSD file:
Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const(0) =
24
0x05, 0xe2, 0x15, \
0x01, 0x00, 0x00 \
0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00,
0x00, \
0x00, 0x00, 0x00, 0x00, \
0x00, 0x00, 0x00, 0x00, 0x00, 0x00;
Table 100: Input channel (4x)
No. Name Internal value, type Default
1 Channel configuration
see table
2
)
Byte 0
0x00 see table
2
)
2 Channel monitoring
see table
3
)
Byte 0
0x00 see table
3
)
Table 101: Channel configuration
2
)
Internal value Operating modes of the analog inputs, individually configurable
0 Unused (default)
1 Analog input 0 V...10 V
2 Digital input
3 Analog input 0 mA...20 mA
4 Analog input 4 mA...20 mA
5 Analog input -10 V...+10 V
8 Analog input Pt100, -50 °C...+400 °C (2-wire)
Device specifications
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 513

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals