Parameter Value
Common power supply voltage Terminal 6 (positive pole of the process voltage,
signal name UP)
Reference potential for the channels O0 to
O3
Terminal 7 (negative pole of the process voltage,
signal name ZP)
Indication of the output signals 1 yellow LED per channel; the LED is on when
the output signal is high (signal 1).
Only internal logic is powered from CPU.
Outputs are powered from UP/ZP terminals.
Way of operation Non-latching type
Min. output voltage at signal 1 UP - 0.1 V
Output delay (max. at rated load)
0 to 1 50 µs
1 to 0 200 µs
Output data length 1 byte
Output current
Rated current per channel (max.) 0.5 A at UP 24 V DC (resistance, general use
and pilot duty)
Rated current per group (max.) 2 A (4 channels * 0.5 A)
Max. leakage current with signal 0 0.5 mA
Output type Non-protected
Protection type External fuse on each channel
Rated protection fuse (for each channel) On request
Demagnetization when inductive loads are
switched off
Must be performed externally according to driven
load specification
Switching Frequencies
With inductive loads On request
Short-circuit-proof / Overload-proof No
Overload message No
Output current limitation No
Resistance to feedback against 24 V
DC
No
Connection of 2 outputs in parallel Not possible
Max. cable length
Shielded On request
Unshielded On request
Device specifications