Terminal Signal Description
2.5 DI5 Signal of the digital input DI5
2.6 DI6 Signal of the digital input DI6
2.7 DI7 Signal of the digital input DI7
2.8 UP Process voltage UP (24 V DC)
2.9 ZP Process voltage ZP (0 V DC)
3.0 DO0 Signal of the digital output DO0
3.1 DO1 Signal of the digital output DO1
3.2 DO2 Signal of the digital output DO2
3.3 DO3 Signal of the digital output DO3
3.4 DO4 Signal of the digital output DO4
3.5 DO5 Signal of the digital output DO5
3.6 DO6 Signal of the digital output DO6
3.7 DO7 Signal of the digital output DO7
3.8 UP3 Process voltage UP3 (24 V DC)
3.9 ZP Process voltage ZP (0 V DC)
WARNING!
Removal/Insertion under power
The devices are not designed for removal or insertion under power. Because of
unforeseeable consequences, it is not allowed to plug or unplug devices with
the power being ON.
Make sure that all voltage sources (supply and process voltage) are switched
off before you
connect or disconnect any signal or terminal block
remove, mount or replace a module.
Disconnecting any powered devices while energized in a hazardous location
could result in an electric arc, which could create a flammable ignition resulting
in fire or explosion.
Make sure that power is removed and that the area has been thoroughly
checked to ensure that flammable materials are not present prior to proceeding.
The devices must not be opened when in operation. The same applies to the
network interfaces.
NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
Make sure that all voltage sources (supply voltage and process supply
voltage) are switched off before you begin with operations on the system.
Never connect any voltages or signals to reserved terminals (marked with
---). Reserved terminals may carry internal voltages.
For the open-circuit detection (cut wire), each analog input channel is pulled up
to "plus" by a high-resistance resistor. If nothing is connected, the maximum
voltage will be read in then.
Device specifications
Communication interface modules (S500) > Modbus
2022/01/313ADR010278, 3, en_US734