Loading...
Processor module PM5630 PM565
0
PM567
0
PM5675
Usage CANopen master communication, CAN
2A/2B, J1939 protocol, CAN sync
Max. number of variables
allowed
Input variables 2 kB 4 kB 5 kB 5 kB
Output variables 2 kB 4 kB 5 kB 5 kB
Network interface ETH1, ETH2:
Usage Ethernet
Physical link 10/100 base-TX, configurable as
internal switch or independent Inter-
faces
Connection 2x RJ45 socket, provided on
TB56xx-2ETH
LEDs, LCD display, function keys RUN / STOP, status, diagnosis, settings
Number of timers Unlimited
Number of counters Unlimited
Programming languages:
Structured Text ST x
Instruction list IL x
Function Block Diagram FBD x
Ladder Diagram LD x
Sequential function chart
SFC
x
Continuous function chart
(CFC)
x
Remarks:
1)
: The values are for information only and cannot be fulfilled altogether. The available
resources are limited at the end by the maximal downloadable application size for each CPU.
Table 43: Combination of TB56xx-2ETH(-XC) and PM56xx(-XC)
Processor module PM5630 PM5650 PM5670 PM5675
TB5600-2ETH 0 slot 0 slot 0 slot 0 slot
TB5610-2ETH 1 slot 1 slot 1 slot 1 slot
TB5620-2ETH 2 slots 2 slots 2 slots 2 slots
TB5640-2ETH - 4 slots 4 slots 4 slots
TB5660-2ETH - -
6 slots
1
) 6 slots
1
)
Remarks:
The slots can be used for connecting communication modules or AC500-S modules. Note that
only one AC500-S module can be connected at one terminal base.
1
) PM567x must have an index C0.
Device specifications
Processor modules > AC500 (standard)
2022/01/31 3ADR010278, 3, en_US 97

Table of Contents