0x2DDD
Constant TRUE [1] Enable inverter
Automatic setpoint selection active [107]
Frequency setpoint selection
via analog input 2
Digital input 1 [11] Run
Digital input 4 [14]
Digital input 3 [13]
Digital input 2 [12]
Rotational direction reversed [69]
Manual setpoint selection active [106]
Running [50]
Stop active [53]
Output signals
Status signals
Output frequency
Activate AI2 setpoint
Activate AI1 setpoint
Invert rotation
Input signals
Frequency setpoint selection
via keypad
(standard setpoint source)
FunctionTrigger
Frequency setpoint selection
via analog input 1
The status signals can be assigned to digital outputs. 4Congure digital outputs^ 263
①
The change-over is iniated from keypad setpoint (standard setpoint source) to AI1 setpoint.
②
The change-over is iniated from AI1 setpoint to AI2 setpoint.
③
The change-over is iniated from AI2 setpoint to AI1 setpoint since the digital input 3 has a higher priority than the digital input 4.
④
The change-over is iniated to keypad setpoint (standard setpoint source).
Conguring the frequency control
Changing the setpoint source during operaon
Example: Change-over from keypad setpoint to AI1/AI2 setpoint
135