6.2.7 Example: Jog forward/Jog reverse
This example shows the funcons "Jog forward (CW)" and "Jog reverse (CCW)" for Jog opera-
on.
The switch S1 starts the motor in the forward direcon of rotaon. The switch S1 in the
inial posion stops the motor again.
The buon S2 starts the motor in the forward direcon of rotaon with frequency preset
5.
The buon S3 starts the motor in the backward direcon of rotaon with frequency preset
6.
The motor rotates in jog operaon as long as the respecve buon is pressed. If both but-
tons are pressed at the same me, the motor is stopped.
CAUTION!
The jog operaon has a higher priority than the "Run" funcon, all other start commands and
the keypad key .
If jog operaon is acve, the motor cannot be stopped with the previously menoned func-
ons!
The jog operaon is stopped by cancelling the funcons "Jog foward (CW)"/"Jog reverse
(CCW)".
The jog operaon can be interrupted with the "Acvate quick stop" 0x2631:003 (P400.03)
funcon.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Buon S2 Jog foward (CW)
Buon S3 Jog reverse (CCW)
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:010 (P400.10) Jog foward (CW) Digital input 2 [12]
0x2631:011 (P400.11) Jog reverse (CCW) Digital input 3 [13]
0x2631:013 (P400.13) Reverse rotaonal direcon Not connected [0]
0x2911:005 (P450.05) Frequency setpoint presets: Preset 5 15 Hz (is used for jog forward)
0x2911:006 (P450.06) Frequency setpoint presets: Preset 6 10 Hz (is used for jog reverse)
Start, stop and rotang direcon commands
Flexible I/O conguraon of the start, stop and rotang direcon commands
Example: Jog forward/Jog reverse