7.4 Changing the setpoint source during operaon
The inverter receives its setpoint from the selected standard setpoint source. For applicaons
requiring a change-over of the setpoint source during operaon, the funcons listed below
must be congured.
Details
For further details and examples, see the following subchapters.
In case of an acvated network control, the funcons for setpoint change-over
are not acve! If in case of network control no setpoint is dened via the net-
work control word, the standard setpoint source is acve.
Funcon Info
Acvate AI1 setpoint
0x2631:014 (P400.14)
Acvate analog input 1 as setpoint source.
4Analog input 1 ^ 255
4Example: Change-over from keypad setpoint to AI1/AI2 setpoint ^ 134
Acvate AI2 setpoint
0x2631:015 (P400.15)
Acvate analog input 2 as setpoint source.
4Analog input 2 ^ 260
4Example: Change-over from keypad setpoint to AI1/AI2 setpoint ^ 134
Acvate keypad setpoint
0x2631:016 (P400.16)
Acvate keypad as setpoint source.
•
The keypad setpoint can be changed in the operang mode via the navigaon keys and keypad key.
4Keypad ^ 86
4Example: Change-over from AI1 setpoint to keypad setpoint ^ 136
Acvate network setpoint
0x2631:017 (P400.17)
Acvate network as setpoint source.
4Dene setpoint via network ^ 296
Acvate preset (bit 0)
0x2631:018 (P400.18)
Acvate parameterisable setpoints (presets) as setpoint source.
•
15 frequency setpoints and 8 PID setpoints can be set as presets.
•
A preset can be selected binary-coded via the four funcons "Acvate preset (bit 0)" ... "Acvate preset (bit
3)".
4Setpoint presets ^ 87
4Example: Change-over from keypad setpoint to preset 1 ... 7 ^ 138
Acvate preset (bit 1)
0x2631:019 (P400.19)
Acvate preset (bit 2)
0x2631:020 (P400.20)
Acvate preset (bit 3)
0x2631:021 (P400.21)
Acvate setpoint via HTL input
0x2631:022 (P400.22)
The digital inputs DI3 and DI4 can be congured as HTL input to evaluate the signal of a cost-eecve HTL
encoder or a reference frequency ("pulse train").
4HTL encoder ^ 162
4Congure digital inputs DI3/DI4 for detecng a pulse train ^ 247
Acvate MOP setpoint
0x2631:025 (P400.25)
The "Motor potenometer" funcon can be used as an alternave setpoint control that is controlled via two
funcons: "MOP setpoint up" and "MOP setpoint down".
4Motor potenometer (MOP) ^ 89
4Example: Change-over from AI1 setpoint to MOP setpoint ^ 141
Acvate segment setpoint (bit 0)
0x2631:026 (P400.26)
Acvate parameterisable segment setpoints as setpoint source.
•
The four funcons "Acvate segment setpoint (bit 0)" ... " Acvate segment setpoint´(bit 3)" enable a set-
point change-over to a segment setpoint parameterised for the "sequencer" funcon during normal opera-
on (no sequence acve).
4Segment conguraon ^ 93
Acvate segment setpoint (bit 1)
0x2631:027 (P400.27)
Acvate segment setpoint (bit 2)
0x2631:028 (P400.28)
Acvate segment setpoint´(bit 3)
0x2631:029 (P400.29)
Diagnosc parameters:
•
0x282B:002 (P125.02): Acve setpoint source
Conguring the frequency control
Changing the setpoint source during operaon
130