7.4 Changing the setpoint source during operaon
The inverter receives its setpoint from the selected standard setpoint source. For applicaons
requiring a change-over of the setpoint source during operaon, the funcons listed below
must be congured.
Details
For further details and examples, see the following subchapters.
In case of an acvated network control, the funcons for setpoint change-over
are not acve! If in case of network control no setpoint is dened via the net-
work control word, the standard setpoint source is acve.
Funcon Info
Acvate AI1 setpoint
0x2631:014 (P400.14)
Acvate analog input 1 as setpoint source.
4Analog input 1 ^ 255
4Example: Change-over from keypad setpoint to AI1/AI2 setpoint ^ 134
Acvate AI2 setpoint
0x2631:015 (P400.15)
Acvate analog input 2 as setpoint source.
4Analog input 2 ^ 260
4Example: Change-over from keypad setpoint to AI1/AI2 setpoint ^ 134
Acvate keypad setpoint
0x2631:016 (P400.16)
Acvate keypad as setpoint source.
The keypad setpoint can be changed in the operang mode via the navigaon keys and keypad key.
4Keypad ^ 86
4Example: Change-over from AI1 setpoint to keypad setpoint ^ 136
Acvate network setpoint
0x2631:017 (P400.17)
Acvate network as setpoint source.
4Dene setpoint via network ^ 296
Acvate preset (bit 0)
0x2631:018 (P400.18)
Acvate parameterisable setpoints (presets) as setpoint source.
15 frequency setpoints and 8 PID setpoints can be set as presets.
A preset can be selected binary-coded via the four funcons "Acvate preset (bit 0)" ... "Acvate preset (bit
3)".
4Setpoint presets ^ 87
4Example: Change-over from keypad setpoint to preset 1 ... 7 ^ 138
Acvate preset (bit 1)
0x2631:019 (P400.19)
Acvate preset (bit 2)
0x2631:020 (P400.20)
Acvate preset (bit 3)
0x2631:021 (P400.21)
Acvate setpoint via HTL input
0x2631:022 (P400.22)
The digital inputs DI3 and DI4 can be congured as HTL input to evaluate the signal of a cost-eecve HTL
encoder or a reference frequency ("pulse train").
4HTL encoder ^ 162
4Congure digital inputs DI3/DI4 for detecng a pulse train ^ 247
Acvate MOP setpoint
0x2631:025 (P400.25)
The "Motor potenometer" funcon can be used as an alternave setpoint control that is controlled via two
funcons: "MOP setpoint up" and "MOP setpoint down".
4Motor potenometer (MOP) ^ 89
4Example: Change-over from AI1 setpoint to MOP setpoint ^ 141
Acvate segment setpoint (bit 0)
0x2631:026 (P400.26)
Acvate parameterisable segment setpoints as setpoint source.
The four funcons "Acvate segment setpoint (bit 0)" ... " Acvate segment setpoint´(bit 3)" enable a set-
point change-over to a segment setpoint parameterised for the "sequencer" funcon during normal opera-
on (no sequence acve).
4Segment conguraon ^ 93
Acvate segment setpoint (bit 1)
0x2631:027 (P400.27)
Acvate segment setpoint (bit 2)
0x2631:028 (P400.28)
Acvate segment setpoint´(bit 3)
0x2631:029 (P400.29)
Diagnosc parameters:
0x282B:002 (P125.02): Acve setpoint source
Conguring the frequency control
Changing the setpoint source during operaon
130