12.13.4 Monitoring
The response to the missing Modbus messages, conguraon errors and inialisaon errors
can be congured via the following parameters.
The parameters for seng network monitoring funcons are described below.
Parameter
Address Name / seng range / [default seng] Info
0x23B1:010
(P510.10)
Modbus -TCP/IP sengs: Ethernet me-out
(MBTCP sengs: Ethernet meout)
0 ... [10] ... 65535 s
•
From version 04.00
Seng of the maximum permissible me-out of the TCP communica-
on.
When the specied monitoring me has elapsed, the response set in
0x2859:007 (P515.07) is triggered in the inverter.
0x23B6:001
(P514.01)
Time-out monitoring: Time-out me
(MBTCP t-out mon: Time-out me)
0.0 ... [2.0] ... 300.0 s
•
From version 04.00
Monitoring is acve if the rst valid write command arrives at the Mod-
bus master. Each further valid write/read message resets the watchdog
mer.
Monitoring responds if within the me set here no valid message has
been received by the Modbus master.
0x23B6:002
(P514.02)
Time-out monitoring: Keep alive me-out me
(MBTCP t-out mon: Keep al t-out)
0.0 ... [2.0] ... 300.0 s
•
From version 04.00
Monitoring is acve aer a valid value is wrien into the keep alive reg-
ister 0x23B6:005 (P514.05) via the Modbus for the rst me.
Keep alive monitoring responds if no value (range 1 ... 65535) has been
wrien into the keep alive register within the me set here.
0x23B6:005
(P514.05)
Time-out monitoring: Keep alive register
(MBTCP t-out mon: Keep al register)
0 ... [0] ... 65535
•
From version 04.00
Time-out monitoring of the keep alive register is acve aer a value has
been wrien into the keep alive register for the rst me.
In order to prevent that me-out monitoring for the keep alive register
responds, the keep alive register must be wrien as follows:
•
With a value of 1 ... 65535 and
•
an interval that is shorter than the me set in 0x23B6:002 (P514.02).
0x2859:003
(P515.03)
Modbus TCP/IP monitoring: Conguraon error
(MBTCP monitoring: Cong error)
•
From version 04.00
Selecon of the response triggered by the recepon of invalid congura-
on data.
Associated error code:
•
33414 | 0x8286 - Network: PDO mapping error
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:004
(P515.04)
Modbus TCP/IP monitoring: Inialisaon error
(MBTCP monitoring: Init error)
•
From version 04.00
Selecon of the response triggered by the occurrence of an error during
the inialisaon of the network component.
Associated error code:
•
33170 | 0x8192 - Network: inialisaon error
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:007
(P515.07)
Modbus TCP/IP monitoring: Fault reacon by me-out
Network
(MBTCP monitoring: React t-out netw)
•
From version 04.00
If monitoring detects a me-out of the TCP communicaon with an exist-
ing TCP connecon, the error response to be selected with this parame-
ter occurs.
The maximum permissible me-out of the TCP communicaon is dened
in 0x23B1:010 (P510.10).
Associated error code:
•
33044 | 0x8114 - Network: overall communicaon meout
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
Conguring the network
Modbus TCP
Monitoring
439