EasyManua.ls Logo

Lenze i550

Lenze i550
704 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.13.4 Monitoring
The response to the missing Modbus messages, conguraon errors and inialisaon errors
can be congured via the following parameters.
The parameters for seng network monitoring funcons are described below.
Parameter
Address Name / seng range / [default seng] Info
0x23B1:010
(P510.10)
Modbus -TCP/IP sengs: Ethernet me-out
(MBTCP sengs: Ethernet meout)
0 ... [10] ... 65535 s
From version 04.00
Seng of the maximum permissible me-out of the TCP communica-
on.
When the specied monitoring me has elapsed, the response set in
0x2859:007 (P515.07) is triggered in the inverter.
0x23B6:001
(P514.01)
Time-out monitoring: Time-out me
(MBTCP t-out mon: Time-out me)
0.0 ... [2.0] ... 300.0 s
From version 04.00
Monitoring is acve if the rst valid write command arrives at the Mod-
bus master. Each further valid write/read message resets the watchdog
mer.
Monitoring responds if within the me set here no valid message has
been received by the Modbus master.
0x23B6:002
(P514.02)
Time-out monitoring: Keep alive me-out me
(MBTCP t-out mon: Keep al t-out)
0.0 ... [2.0] ... 300.0 s
From version 04.00
Monitoring is acve aer a valid value is wrien into the keep alive reg-
ister 0x23B6:005 (P514.05) via the Modbus for the rst me.
Keep alive monitoring responds if no value (range 1 ... 65535) has been
wrien into the keep alive register within the me set here.
0x23B6:005
(P514.05)
Time-out monitoring: Keep alive register
(MBTCP t-out mon: Keep al register)
0 ... [0] ... 65535
From version 04.00
Time-out monitoring of the keep alive register is acve aer a value has
been wrien into the keep alive register for the rst me.
In order to prevent that me-out monitoring for the keep alive register
responds, the keep alive register must be wrien as follows:
With a value of 1 ... 65535 and
an interval that is shorter than the me set in 0x23B6:002 (P514.02).
0x2859:003
(P515.03)
Modbus TCP/IP monitoring: Conguraon error
(MBTCP monitoring: Cong error)
From version 04.00
Selecon of the response triggered by the recepon of invalid congura-
on data.
Associated error code:
33414 | 0x8286 - Network: PDO mapping error
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:004
(P515.04)
Modbus TCP/IP monitoring: Inialisaon error
(MBTCP monitoring: Init error)
From version 04.00
Selecon of the response triggered by the occurrence of an error during
the inialisaon of the network component.
Associated error code:
33170 | 0x8192 - Network: inialisaon error
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:007
(P515.07)
Modbus TCP/IP monitoring: Fault reacon by me-out
Network
(MBTCP monitoring: React t-out netw)
From version 04.00
If monitoring detects a me-out of the TCP communicaon with an exist-
ing TCP connecon, the error response to be selected with this parame-
ter occurs.
The maximum permissible me-out of the TCP communicaon is dened
in 0x23B1:010 (P510.10).
Associated error code:
33044 | 0x8114 - Network: overall communicaon meout
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
Conguring the network
Modbus TCP
Monitoring
439

Table of Contents

Other manuals for Lenze i550

Related product manuals