EasyManua.ls Logo

Lenze i550

Lenze i550
704 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18.8 3-phase mains connecon 480 V
18.8.1 Rated data
The output currents apply to these operang condions:
At a switching frequency of 2 kHz or 4 kHz: Max. ambient temperature 45°C.
At a switching frequency of 8 kHz or 16 kHz: Max. ambient temperature 40 °C.
Inverter I55AE137F I55AE155F I55AE175F I55AE211F I55AE215F I55AE222F
Rated power kW 0.37 0.55 0.75 1.1 1.5 2.2
Rated power hp 0.5 0.75 1 1.5 2 3
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0-400/480 V
Rated mains current
Without mains choke A 1.5 2.1 2.8 3.7 4.5 6.5
With mains choke A 1.2 1.7 2.2 2.5 3.1 4.4
Apparent output power kVA 0.9 1.2 1.6 2.2 2.6 3.8
Rated output current
2 kHz A - 1.6 2.1 3 3.5 4.8
4 kHz A 1.1 1.6 2.1 3 3.5 4.8
8 kHz A 1.1 1.6 2.1 3 3.5 4.8
16 kHz A 0.7 1.1 1.4 2 2.3 3.2
Power loss
2 kHz W - 24 30 38 45 62
4 kHz W 20 25 32 40 48 66
8 kHz W 24 31 40 51 61 85
16 kHz W 24 31 40 51 61 85
For controller inhibit W 6 6 6 6 6 6
Cyclic mains switching 3 mes per minute
Max. Motor cable length shielded
Without EMC category m 15 50 50 50 50 50
Category C1 (2 kHz, 4 kHz, 8
kHz)
m 3 3 3 - - -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 15 20 20 20 20 20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 15 20 20 35 35 35
Weight kg 0.8 1 1 1.35 1.35 1.35
Weight lb 1.8 2.2 2.2 3 3 3
Technical data
3-phase mains connecon 480 V
Rated data
653

Table of Contents

Other manuals for Lenze i550

Related product manuals