Address Name / seng range / [default seng] Info
0x2636:010
(P430.10)
Analog input 1: Error response
(Analog input 1: AI1 error resp.)
Error response for analog input 1.
•
The selected response takes place if the monitoring condion selected
in 0x2636:009 (P430.09) is met for at least 500 ms.
Associated error code:
•
28801 | 0x7081 - Analog input 1 fault
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2636:011
(P430.11)
Analog input 1: Min torque value
(Analog input 1: Min. torque)
-400.0 ... [0.0] ... 400.0 %
•
From version 03.00
Denion of the seng range for operang mode "MS: Torque mode".
•
100 % ≡ permissible maximum torque 0x6072 (P326.00)
•
Direcon of rotaon according to sign.
•
The standard setpoint source for operang mode 0x6060 (P301.00) =
"MS: Torque mode [-1]" is selected in 0x2860:003 (P201.03).
4Conguring the torque control ^ 149
0x2636:012
(P430.12)
Analog input 1: Max torque value
(Analog input 1: Max. torque)
-400.0 ... [100.0] ... 400.0 %
•
From version 03.00
11.2.1.1 Example: Input range 0 ... 10 V ≡ seng range 0 ... 50 Hz
In this conguraon, for instance, a frequency setpoint between 0 and 50 Hz can be set with a
potenometer connected to the analog input.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint denion
(Input voltage 1 V ≡ 5 Hz)
Parameter Designaon Seng for this example
0x2636:001 (P430.01) Analog input 1: Input range 0 ... 10 VDC [0]
0x2636:002 (P430.02) Analog input 1: Min frequency value 0.0 Hz
0x2636:003 (P430.03) Analog input 1: Max frequency value 50.0 Hz
0x2636:006 (P430.06) Analog input 1: Filter me 10 ms
100
0
50
[Hz]
[%]
0
10
0
100
[%]
[V]
0
AI1
%
Hz
V
%
10 ms0 ... 10 VDC 0 ... 50 Hz
I/O extensions and control connecons
Congure analog inputs
Analog input 1