18.5 3-phase mains connecon 230/240 V "Light Duty"
18.5.1 Rated data
The output currents apply to these operang condions:
•
At a switching frequency of 2 kHz or 4 kHz: Ambient temperature above 40 °C with a rated
output current reduced by 2.5 %/°C.
•
If the load characterisc "Light Duty" and the switching frequencies 8 kHz or 16 kHz are
selected, only the values of the load characterisc "Heavy Duty" are reached.
Inverter I55AE240C I55AE255C
Rated power kW 5.5 7.5
Rated power hp 7.5 10
Mains voltage range 3/PE AC 170 V ... 264 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0-230/240 V
Rated mains current
Without mains choke A 25.8 -
With mains choke A 18.9 24.2
Apparent output power kVA 8 10.5
Rated output current
2 kHz A 20.6 27.6
4 kHz A 20.6 27.6
8 kHz A - -
16 kHz A - -
Power loss
2 kHz W 124 190
4 kHz W 131 200
8 kHz W - -
16 kHz W - -
For controller inhibit W 6 6
Cyclic mains switching 3 mes per minute
Max. Motor cable length shielded
Without EMC category m 50 50
Category C1 (2 kHz, 4 kHz, 8
kHz)
m - -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m - -
Category C3 (2 kHz, 4 kHz, 8
kHz)
m - -
Weight kg 2.1 2.1
Weight lb 4.6 4.6
Technical data
3-phase mains connecon 230/240 V "Light Duty"
Rated data
645