4.Connect to the Lenze controller online.
5.Select 'Safe parameter set in the device (F6)'.
The Lenze controller then starts uploading the parameters of all its EtherCAT slaves (includ-
ing i550 EtherCAT) and stores these parameters together with its own parameter set in its
boot project. The stored parameter set for the i550 EtherCAT is automacally wrien to the
inverter by the controller when the Lenze controller powers up aer mains connecon.
If the modied parameter set from the inverter should correspond to the »PLC
Designer« project:
6.Log in to the Lenze controller.
7.If the dialogue displays dierences in the parameter selecon, select Upload all.
8.Save the »PLC Designer« project.
12.10.6 Monitoring
The parameters for seng network monitoring funcons are described below.
Parameter
Address Name / seng range / [default seng] Info
0x2859:001
(P515.01)
EtherCAT monitoring: Watchdog elapsed
(EtherCAT monit.: WD elapsed)
From version 02.00
Selecon of the response to the connuous interrupon of communica-
on to the EtherCAT master, e. g. by cable break or failure of the Ether-
CAT master.
Associated error code:
33168 | 0x8190 - Network: watchdog meout
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:003
(P515.03)
EtherCAT monitoring: Invalid conguraon
(EtherCAT monit.: Invalid cong)
From version 02.00
Selecon of the response triggered by the recepon of invalid congura-
on data.
Associated error code:
33414 | 0x8286 - Network: PDO mapping error
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:004
(P515.04)
EtherCAT monitoring: Inialisaon error
(EtherCAT monit.: Init. error)
From version 02.00
Selecon of the response triggered by the occurrence of an error during
the inialisaon of the network component.
Associated error code:
33170 | 0x8192 - Network: inialisaon error
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:005
(P515.05)
EtherCAT monitoring: Invalid process data
(EtherCAT monit.: Inval. proc.data)
From version 02.00
Selecon of the response triggered by the recepon of invalid process
data.
Associated error code:
33171 | 0x8193 - Network: invalid cyclic process data
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
Conguring the network
EtherCAT
Monitoring
388