33155 0x8183 CAN: warning Keypad display: CAN bus warning
Cause Error type/response Remedy
Too many faulty frames have been received.
•
Defecve cable (e. g. loose contact).
•
Two nodes with the same node address.
Warning (Congurable)
•
Check wiring of the network.
•
Check bus terminang resistor.
•
Set the idencal baud rate for each node of
the network.
•
Assign a unique node address to each node
of the network.
•
Eliminate EMC interferences.
Seng parameters: 0x2857:011
33156 0x8184 CAN: heartbeat me-out consumer 1 Keypad display: CAN heartb. C1
Cause Error type/response Remedy
Within the heartbeat me 0x1016:001
(P520.01), no heartbeat telegram was received
by node 1 to be monitored.
Fault (Congurable)
•
Check communicaon with the heartbeat
producer.
•
Reacvate heartbeat producer.
Seng parameters: 0x2857:005
Related topics
4Heartbeat protocol ^ 361
33157 0x8185 CAN: heartbeat me-out consumer 2 Keypad display: CAN heartb. C2
Cause Error type/response Remedy
Within the heartbeat me 0x1016:002
(P520.02), no heartbeat telegram was received
by node 2 to be monitored.
Fault (Congurable)
•
Check communicaon with the heartbeat
producer.
•
Reacvate heartbeat producer.
Seng parameters: 0x2857:006
Related topics
4Heartbeat protocol ^ 361
33158 0x8186 CAN: heartbeat me-out consumer 3 Keypad display: CAN heartb. C3
Cause Error type/response Remedy
Within the heartbeat me 0x1016:003
(P520.03), no heartbeat telegram was received
by node 3 to be monitored.
Fault (Congurable)
•
Check communicaon with the heartbeat
producer.
•
Reacvate heartbeat producer.
Seng parameters: 0x2857:007
Related topics
4Heartbeat protocol ^ 361
33159 0x8187 CAN: heartbeat me-out consumer 4 Keypad display: CAN heartb. C4
Cause Error type/response Remedy
Within the heartbeat me 0x1016:004
(P520.04), no heartbeat telegram was received
by node 4 to be monitored.
Fault (Congurable)
•
Check communicaon with the heartbeat
producer.
•
Reacvate heartbeat producer.
Seng parameters: 0x2857:008
Related topics
4Heartbeat protocol ^ 361
33168 0x8190 Network: watchdog meout Keypad display: Watchdog meout
Cause Error type/response Remedy
Time-out during cyclic data recepon, e.g. due
to an interrupted communicaon link to the
master or missing cyclic data.
Trouble (Congurable)
•
Check wiring of the network.
•
Eliminate EMC interferences.
Seng parameters:
0x2859:001 (P515.01) (PROFIBUS)
0x2859:001 (P515.01) (EtherCAT)
0x2859:001 (P515.01) (EtherNet/IP)
0x2859:001 (P515.01) (PROFINET)
0x2859:001 (POWERLINK)
Diagnoscs and fault eliminaon
Error codes, causes and remedies
630