7.4.4 Example: Change-over from AI1 setpoint to MOP setpoint
The "Acvate MOP setpoint" funcon enables a setpoint change-over to the motor poten-
ometer during operaon.
Precondions
A setpoint change-over to the motor potenometer is only eected if
no setpoint source with a higher priority has been selected. 4Priority of the setpoint sour-
ces^ 131
no jog operaon is acve ("Jog foward (CW)" and "Jog reverse (CCW)" funcons).
Example for operang mode
The analog input 1 is set as standard setpoint source.
Switch S1 starts the motor in forward direcon of rotaon. Switch S1 in the inial posion
stops the motor again.
Switch S2 acvates the motor potenometer as setpoint source. The MOP setpoint can
then be increased via buon S3 and reduced via buon S4. If both buons are pressed at
the same me, the MOP setpoint remains unchanged.
Switch S5 switches the direcon of rotaon.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S4 S5S3 S4
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Switch S2 Acvate MOP setpoint
Buon S3 MOP setpoint up
Buon S4 MOP setpoint down
Switch S5 Reverse rotaonal direcon
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:025 (P400.25) Acvate MOP setpoint Digital input 2 [12]
0x2631:023 (P400.23) MOP setpoint up Digital input 3 [13]
0x2631:024 (P400.24) MOP setpoint down Digital input 4 [14]
0x2631:013 (P400.13) Reverse rotaonal direcon Digital input 5 [15]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2838:003 (P203.03) Stop method Standard ramp [1]
0x2860:001 (P201.01) Frequency control: Default setpoint source Analog input 1 [2]
0x2917 (P220.00) Acceleraon me 1 1.0 s
0x2918 (P221.00) Deceleraon me 1 1.0 s
0x2919 (P222.00) Acceleraon me 2 4.0 s (for MOP setpoint change)
0x291A (P223.00) Deceleraon me 2 4.0 s (for MOP setpoint change)
0x4003 (P413.00) MOP starng mode Starng value [1]
0x4004:001 (P414.01) MOP starng values: Frequency 20 Hz
Conguring the frequency control