EasyManua.ls Logo

Lenze i550

Lenze i550
704 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Address Name / seng range / [default seng] Info
0x261C:050
(P740.50)
Favorites sengs: Parameter 50
(Favorites se.: Parameter 50)
0x00000000 ... [0x29110400] ... 0xFFFFFF00
4.5 Saving the parameter sengs
4.5.1 Save parameter sengs with keypad
If one parameter seng has been changed with the keypad but has not been saved in the
memory module with mains failure protecon, the SET display is blinking.
In order to save parameter sengs in the user memory of the memory module, press the key-
pad enter key for more than 3 s.
MAN MAN MANAUTO AUTO AUTOLOC LOC LOCREM REM REM
VEL
Saving Parameters Parameters S aved
:FLEX:AIN1
SET SET SET
> 3 s
0 0 0 S T O P S A V I N G P S P
S
A
V
E D
4.5.2 Save parameter sengs with »EASY Starter«
If a parameter seng has been changed with the »EASY Starter« but not yet saved in the
memory medium with mains failure protecon, the status line of the »EASY Starter« displays
the note "The parameter set was changed".
There are 3 opons to save the parameter sengs in the user memory of the storage medium
Click the buon in the toolbar of the »EASY Starter« .
Press the funcon key F6.
Execute the device command "Save user data": 0x2022:003 (P700.03) = "On / start [1]".
4.5.3 Automac storage in the memory module
Parameter
Address Name / seng range / [default seng] Info
0x2829
(P732.00)
Automac storage in the memory module
(Auto-Save EPM)
1 = Acvate automac saving of parameters in the memory module. Sav-
ing is undertaken to a parameter stored on the memory module with
each write cycle. An excessively high number of write cycles reduces the
service life of the memory module.
With the seng 0, the "Save user data" 0x2022:003 (P700.03) device
command must be explicitly executed, or the "Enter" keypad key must
be pressed for longer than 3 s to save the current parameter sengs
in the memory module of the inverter with mains failure protecon.
Warning
The "Automac saving" funcon must not be used together with cyclical
wring of parameters via PDO.
0 Inhibit
1 Enable
Commissioning
Saving the parameter sengs
Automac storage in the memory module
37