Address Name / seng range / [default seng] Info
0x29E0:002 Field weakening controller sengs: Reset me (ASM)
1.0 ... [1478.3]* ... 240000.0 ms
* Default seng depending on the size.
Reset me Tn of the eld weakening controller.
0x29E1 Field weakening controller Field limitaon
5.00 ... [100.00] ... 100.00 %
•
From version 04.00
Field limitaon of the eld weakening controller.
10.7.6.5 ASM eld weakening controller (extended)
For a quick commissioning, the calculaons and sengs are made automacally during the
motor calibraon.
Precondions
The eld weakening controller is only eecve in the following motor control types:
•
Servo control (SC ASM)
•
Sensorless vector control (SLVC)
Parameter
Address Name / seng range / [default seng] Info
0x29E2 DC-bus lter me
1.0 ... [25.0] ... 1000.0 ms
Filter me for the current DC-bus voltage used for eld weakening.
0x29E3 Motor voltage lter me
1.0 ... [25.0] ... 1000.0 ms
Filter me for the current motor voltage used for eld weakening.
0x29E4
(P354.00)
Voltage reserve range
(Voltage reserve)
0 ... [5] ... 20 %
Voltage reserve at the transion point to the eld weakening, with refer-
ence to the current value of the DC-bus voltage.
Has an eect for Servo control (SC ASM) (0x2C00 (P300.00) = 2), Sensor-
less control (SL PSM) (0x2C00 (P300.00) = 3) and at Sensorless vector
control (SLVC) (0x2C00 (P300.00) = 4).
•
100 % ≡ DC bus voltage 0x2D87 (P105.00)
10.7.6.6 PSM eld weakening controller
Parameter
Address Name / seng range / [default seng] Info
0x29E0:003 Field weakening controller sengs: Reset me (PSM)
1.0 ... [800.0]* ... 240000.0 ms
* Default seng depending on the size.
•
From version 05.02
In the me congured (default 800 ms), the swivel control rotates the
current phasor by 90°. Increasing the me makes the system smoother
at the voltage limit. At the same me, it also reduces the dynamics.
Conguring the motor control
Opons for opmising the control loops
Motor control sengs
225