EasyManua.ls Logo

Lenze i550

Lenze i550
704 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.6.2.3 Acvang DC braking manually
By means of the "Acvate DC braking" funcon, DC braking can be acvated manually.
Precondions
The current for DC braking must be set > 0 % so that the funcon can be executed.
Parameter
Address Name / seng range / [default seng] Info
0x2631:005
(P400.05)
Funcon list: Acvate DC braking
(Funcon list: DC braking)
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Acvate DC braking" funcon.
Trigger = TRUE: Acvate DC braking.
Trigger = FALSE: Deacvate DC braking.
CAUTION!
DC braking remains acve as long as the trigger is set to TRUE.
4DC braking^ 196
0 Not connected No trigger assigned (trigger is constantly FALSE).
Example for operang mode
Switch S1 starts the motor in forward direcon of rotaon. Switch S1 in the inial posion
stops the motor again.
Switch S2 acvates DC braking.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Switch S2 Acvate DC braking
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:005 (P400.05) Acvate DC braking Digital input 2 [12]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2838:003 (P203.03) Stop method Standard ramp [1]
0x2860:001 (P201.01) Frequency control: Default setpoint source Analog input 1 [2]
0x2B84:001 (P704.01) DC braking: Current 10 %
Conguring the motor control
Parameterisable motor funcons
DC braking
200

Table of Contents

Other manuals for Lenze i550

Related product manuals