Address Name / seng range / [default seng] Info
0x2DA5:016
(P111.16)
Diagnoscs of analog input 2: Status
(AI2 diagnoscs: AI2 status)
Read only
From version 04.00
Bit-coded display of the status of analog input 2 (X3/AI2).
Bit 0 Mode 0: 0 ... 10 VDC acve
Bit 1 Mode 1: 0 ... 5 VDC acve
Bit 2 Mode 2: 2 ... 10 VDC acve
Bit 3 Mode 3: -10 ... 10 VDC acve
Bit 4 Mode 4: 4 ... 20 mA acve
Bit 5 Mode 5: 0 ... 20 mA acve
Bit 6 24 V supply OK
Bit 7 Calibraon successful
Bit 8 Monitoring threshold exceeded/not reached
Bit 9 Input current too low
Bit 10 Input voltage too low
Bit 11 Input voltage too high
0x2DAA:001
(P112.01)
Diagnoscs of analog output 1: Voltage
(AO1 diagnoscs: AO1 Voltage)
Read only: x.xx V
Display of the current output voltage at X3/AO1.
0x2DAA:002
(P112.02)
Diagnoscs of analog output 1: Current
(AO1 diagnoscs: AO1 Current)
Read only: x.xx mA
Display of the present output current at X3/AO1.
0x2DAB:002
(P113.02)
Diagnoscs of analog output 2: Current
(AO2 diagnoscs: AO2 Voltage)
Read only: x.xx mA
Only available for applicaon I/O.
Display of the present output current at X3/AO2.
0x2DAB:001
(P113.01)
Diagnoscs of analog output 2: Voltage
(AO2 diagnoscs: AO2 Current)
Read only: x.xx V
Only available for applicaon I/O.
Display of the current output voltage at X3/AO2.
Related topics
4Congure analog inputs^ 255
4Congure analog outputs^ 275
17.4.4 Service life diagnoscs
The following parameters provide some informaon about the use of the inverter.
This includes the following informaon:
Operang and power-on me of the inverter/control unit
Operang me of the internal fan
Number of switching cycles of the mains voltage
Number of switching cycles of the relay
Number of short-circuits and earth faults that have occurred
Display of the number of "Imax: Clamp responded too oen" errors that have occurred.
Parameter
Address Name / seng range / [default seng] Info
0x2D81:001
(P151.01)
Life-diagnosis: Operang me
(Life-diagnosis: Operang me)
Read only: x s
Display showing for how long the inverter has been running so far "Oper-
aon enabled" device state).
0x2D81:002
(P151.02)
Life-diagnosis: Power-on me
(Life-diagnosis: Power-on me)
Read only: x s
Display showing for how long the inverter has been supplied with mains
voltage so far.
0x2D81:003
(P151.03)
Life-diagnosis: Control unit operang me
(Life-diagnosis: CU oper. me)
Read only: x ns
Display showing for how long the control unit has been supplied with
voltage so far. This includes the external 24-V supply and voltage supply
via USB module.
0x2D81:004
(P151.04)
Life-diagnosis: Main switching cycles
(Life-diagnosis: Switching cycles)
Read only
Display of the number of switching cycles of the mains voltage.
Diagnoscs and fault eliminaon
Diagnosc parameters
I/O diagnoscs
607