Frequency setpoint selection
PID feedback = setpoint [73]
Output signals
Status signals
Output frequency
Deactivate PID controlling
Enable inverter
Input signals
Process setpoint
FunctionTrigger
The status signals can be assigned to digital outputs. 4Congure digital outputs ^ 263
①
PID control is deacvated: a change-over is iniated from the congured PID control to speed-controlled operaon.
②
PID control is acvated again: a change-over is iniated from speed-controlled operaon back to the congured PID control.
7.3.5 Process controller diagnoscs
The following parameters serve to diagnose the process controller.
Parameter
Address Name / seng range / [default seng] Info
0x401F:001
(P121.01)
Current setpoint
(PID setpoint)
•
Read only: x.xx PID unit
Display of the current reference value (setpoint) for the process control-
ler.
0x401F:002
(P121.02)
Current process variable
(PID process var.)
•
Read only: x.xx PID unit
Display of the current controlled variable (actual value) fed back for the
process controller.
0x401F:003
(P121.03)
Status
(PID status)
•
Read only
Bit-coded status display of the process controller.
Bit 0 Process controller o
Bit 1 PID output set to 0
Bit 2 PID I-component inhibited
Bit 3 PID inuence acve
Bit 4 Setpoint = actual value
Bit 5 Idle state acve
Bit 6 Max. alarm
Bit 7 Min. alarm
0x401F:004 PID control value
•
Read only: x.x Hz
•
From version 03.00
Display of the output frequency aer the PID controller, but without any
inuencing factor.
Conguring the frequency control
Conguring the process controller
Process controller funcon selecon
128