12.1 Control the inverter via network
12.1.1 Acvate network control
In order to be able to control the inverter via network, a trigger must be rst assigned in
0x2631:037 (P400.37) to the "Acvate network control" funcon.
•
This trigger can for instance be the constant value "TRUE" or a digital input.
•
If the assigned trigger is = TRUE, the motor can only be started via the network control
word (excepon: Jog operaon; see chapter "Start, stop and rotang direcon commands"
^ 54).
In case of an acvated network control, the following funcons are sll acve:
•
0x2631:001 (P400.01): Enable inverter
•
0x2631:002 (P400.02): Run
•
0x2631:003 (P400.03): Acvate quick stop
•
0x2631:004 (P400.04): Reset fault
•
0x2631:005 (P400.05): Acvate DC braking
•
0x2631:010 (P400.10): Jog foward (CW)
•
0x2631:011 (P400.11): Jog reverse (CCW)
•
0x2631:012 (P400.12): Acvate keypad control
•
0x2631:037 (P400.37): Acvate network control
•
0x2631:043 (P400.43): Acvate fault 1
•
0x2631:044 (P400.44): Acvate fault 2
•
0x2631:054 (P400.54): Posion counter reset
All other funcons congurable via 0x2631:xx (P400.xx) are deacvated in case of network
control.
Parameter
Address Name / seng range / [default seng] Info
0x2631:037
(P400.37)
Funcon list: Acvate network control
(Funcon list: Network control)
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Acvate network control" funcon.
Trigger = TRUE: Acvate network control.
Trigger = FALSE: no acon / deacvate network control again.
0 Not connected No trigger assigned (trigger is constantly FALSE).
114 Network control acve (from version 02.00) TRUE if the network control is requested via bit 5 of the AC drive control
word 0x400B:001 (P592.01). Otherwise FALSE.
Notes:
•
Set this selecon if the network control is to be acvated via bit 5 of
the AC drive control word.
•
The AC drive control word can be used with any communicaon pro-
tocol.
4AC drive control word ^ 328
Conguring the network
Control the inverter via network
Acvate network control
281