10.5.1 Required commissioning steps
1.
Conguring the feedback system ^ 161
2.
Acvate motor control type: 0x2C00 (P300.00) = "V/f characterisc control (VFC closed
loop) [7]".
3.
Set liming factors for the V/f characterisc:
1.
Rated mains voltage 0x2540:001 (P208.01)
2.
Minimum frequency 0x2915 (P210.00)
3.
Maximum frequency 0x2916 (P211.00)
4.
Set V/f characterisc data:
1.
Base voltage 0x2B01:001 (P303.01)
2.
Base frequency 0x2B01:002 (P303.02)
5.
Select a characterisc shape suitable for the applicaon in 0x2B00 (P302.00).
6.
Oponal sengs:
•
Set voltage boost ^ 182
•
Set oscillaon damping ^ 184
•
Opmising the stalling behaviour ^ 185
•
Addive voltage impression ^ 190
•
Slip controller ^ 227
7.
Oponal: carry out opmisaon of the control circuits.
•
A opmisaon of the control loops is not mandatory for this motor control type but
may lead to a beer control mode.
•
Details: 4
Opons for opmising the control loops ^ 213
Conguring the motor control
V/f characterisc control for asynchronous motor (VFC closed loop)
Required commissioning steps
193