5.6 Stopping performance
In the default seng, the motor is brought to a standsll aer a stop command with standard
ramp. Alternavely, coasng, ramping down with quick stop ramp or a switch-o posioning
can be selected.
Details
The stop method can be selected in 0x2838:003 (P203.03). The following diagram demon-
strates the dierent stop methods:
t
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
t
t
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
t
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
0x2838:003
0x2838:003
0x2838:003
0x2838:003
0x2DDD
= switch-off positioning [3]
= quick stop ramp [2]
= standard ramp [1]
= coasting [0]
Digital input 2 [12] Run
Digital input 1 [11]
Output signals
Output frequency
Enable inverter
Input signals
Frequency setpoint selection
FunctionTrigger
①
Stop method = "Coasng [0]": The motor coasts down.
②
Stop method = "Standard ramp [1]": The motor is brought to standsll with a deceleraon me 1 (here: 10 s).
③
Stop method = "Quick stop ramp [2]": The motor is brought to a standsll with the deceleraon me for quick stop (here: 1 s).
④
Stop method = "Switch-o posioning [3]": this method is similar to the stop method "Standard ramp". Depending on the current output
frequency, however, the inverter delays the beginning of the down-ramping so that the number of motor revoluons unl a standsll is
reached and thus the stopping posion is always relavely constant.
⑤
If "Enable inverter" is set to FALSE, the inverter is disabled. The motor becomes torqueless and coasts to standsll depending on the mass
inera of the machine (irrespecve of the set stop method).
Basic seng
Stopping performance
46