12.16.2 Basic seng and opons
12.16.2.1 Staon name and IP conguraon
The staon name and the IP conguraon can be assigned via the IO-Controller. These set-
tings enable the IO-Controller to idenfy the inverter in the network and manage the data
exchange.
The staon name and the IP conguraon can also be assigned via the »EASY Starter«:
The staon name of the inverter must be entered with permissible characters according to
the PROFINET specicaon. 40x2381:004 (P510.04)
Display of the currently used
staon name: 40x2382:004 (P511.04)
The IP conguraon comprises the assignments of:
IP address 0x2381:001 (P510.01)
Subnet mask 0x2381:002 (P510.02)
Gateway address 0x2381:003 (P510.03)
Display of the currently used IP conguraon: 40x2382:001 (P511.01) ... 0x2382:003
(P511.03)
Save the staon name and the IP conguraon in the inverter with mains failure
protecon in order that the inverter can be idened via Ethernet if the IO Con-
troller is switched o. 0x2022:003 (P700.03)
See: 4Saving the parameter sengs ^ 37
An invalid staon name or the assignment of invalid combinaons of IP address,
subnet mask and gateway address may prevent a connecon to PROFINET.
In case of impermissible sengs, the red LED "BUS ERR" is blinking and the
error message "PROFINET: stack inialisaon error [0x8192]" is displayed.
4LED status display ^ 492
Parameter
Address Name / seng range / [default seng] Info
0x2381:001
(P510.01)
PROFINET sengs: IP address
(PROFINET se.: IP address)
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
From version 02.00
Set IP address
A changed value will only be eecve aer the PROFINET communica-
on is restarted (0x2380 (P508.00) = 1).
0x2381:002
(P510.02)
PROFINET sengs: Subnet
(PROFINET se.: Subnet)
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
From version 02.00
Set subnet mask
A changed value will only be eecve aer the PROFINET communica-
on is restarted (0x2380 (P508.00) = 1).
0x2381:003
(P510.03)
PROFINET sengs: Gateway
(PROFINET se.: Gateway)
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
From version 02.00
Set gateway address
A changed value will only be eecve aer the PROFINET communica-
on is restarted (0x2380 (P508.00) = 1).
The gateway address is valid if the network address of the IP address
is idencal to the gateway address. In this case, no gateway funcon-
ality is used.
DHCP is not supported.
0x2381:004
(P510.04)
PROFINET sengs: Staon name
(PROFINET se.: Staon name)
From version 02.00
Set staon name
A changed value will only be eecve aer the PROFINET communica-
on is restarted (0x2380 (P508.00) = 1).
0x2381:005 PROFINET sengs: I&M1 System designaon
From version 02.00
Input/output of the I&M1 system designaon
The default seng is an empty string.
0x2381:006 PROFINET sengs: I&M1 Installaon site
From version 02.00
Input/output of the I&M1 locaon idencaon code
The default seng is an empty string.
0x2381:007 PROFINET sengs: I&M2 Installaon date
From version 02.00
Input/output of the I&M2 date of installaon
The default seng is an empty string.
0x2381:008 PROFINET sengs: I&M3 addional informaon
From version 02.00
Input/output of the I&M3 addional informaon
The default seng is an empty string.
0x2381:009 PROFINET sengs: I&M4 signature code
From version 02.00
Input/output of the I&M4 signature
The default seng is an empty string.
Conguring the network
PROFINET
Basic seng and opons
484