12.15.2 Basic seng and opons
12.15.2.1 Staon address seng
Each network node must be provided with a unique staon address.
Details
The staon address of the inverter can be oponally set via the DIP switches on the device
labelled with "1" ... "64" or in 0x2341:001 (P510.01). (The DIP switches have priority.)
The seng that is acve when the inverter is switched on is the eecve seng.
The labelling of the DIP switches corresponds to the values of the individual DIP switches
for determining the staon address (see the following example).
The acve staon address is shown in 0x2342:001 (P511.01).
View of the DIP switch
Address
O
N
32 16 8
4
64
2 1
PROFIBUS
Example of how the staon address is set via the DIP switches
DIP switch 64 32 16 8 4 2 1
Seng OFF OFF ON OFF ON ON ON
Value 0 0 16 0 4 2 1
Staon address = sum of all values = 16 + 4 + 2 + 1 = 23
Parameter
Address Name / seng range / [default seng] Info
0x2341:001
(P510.01)
PROFIBUS sengs: Staon address
(PROFIBUS se.: Staon address)
1 ... [3] ... 125
Oponal seng of the staon address (instead of seng via DIP
switches 1 ... 64).
The staon address set here only becomes eecve if DIP switches
1 ... 64 have been set to OFF before mains switching.
A change in the staon address only becomes eecve aer a restart
of PROFIBUS communicaon.
12.15.2.2 Baud rate seng
At the class 1 DP master, the desired baud rate is set. All masters at the bus must be set to the
same baud rate.
Details
The inverter detects the baud rate automacally.
The acve baud rate is displayed in 0x2342:002 (P511.02).
The status of automac detecon is displayed in 0x2348:002 (P516.02).
Conguring the network
PROFIBUS
Basic seng and opons