12.10.5 Parameter download
Parameter sengs are not stored in a power failure safe manner when using the inverter as a
system drive in the Lenze system. All inverter sengs that deviate from the Lenze default set-
ting are held centrally in the Lenze controller and saved there persistently. All parameters are
transferred from the Lenze controller to the inverter during inializaon upon start-up.
All size-dependent parameters are not downloaded.
The parameters of the inverter are managed in the »PLC Designer« project. The »PLC
Designer« project, including the parameters, is saved on the engineering PC using the storage
funcon of »PLC Designer«. The »PLC Designer« transfers the parameters to the Lenze con-
troller when the controller is logged on to. The controller passes the parameter sets to the
subordinate controller. The parameter sets are wrien back to the inverter by the Lenze con-
troller every me the system starts.
There are three applicaon for managing and modifying parameters:
•
Modifying the parameters of an inverter online:
-
If a parameter is modied online, the »PLC Designer« writes the parameter directly to
the corresponding inverter and simultaneously modies the parameter in the »PLC
Designer«- project.
The parameter modicaon is not registered in the Lenze controller. The param-
eter modicaon in the inverter is lost when the controller is cold-started. Log
out and log back in again with the »PLC Designer« to avoid this. (Menu com-
mands: Online → Log out / Online → Log in)
-
In this case, the complete parameter set is wrien to the controller and transferred to
the inverter.
-
The parameter set is only available in the inverter and controller aer the transfer by
logging in unl the system is next shut down (not stored in a power failure safe man-
ner).
•
Modifying the parameters of an inverter oine:
-
If a parameter is modied oine, the »PLC Designer« modies the value directly in
the »PLC Designer« project. When logging into the Lenze controller, the complete
parameter set is wrien to the controller. It then transfers the parameter set to the
inverter.
-
The parameter set is only available in the inverter and controller aer the transfer by
logging in unl the system is next shut down (not stored in a power failure safe man-
ner).
•
Saving the parameters of the inverter in the Lenze controller so that they remain in the
device aer switching o:
-
A separate parameter set for the subordinate inverters is available in the boot project
of the Lenze controller. It is only updated if the "Create boot project" funcon is execu-
ted via the »PLC Designer«. The current parameterisaon is then saved and is available
aer the mains connecon. The stored parameter set is automacally wrien to the
inverter by the controller at boot-up following mains connecon.
-
If a boot project exists on the Lenze controller, the parameters of the inverter can also
be modied with »EASY Starter« and stored permanently.
Modifying parameters and permanently storing them.
1.Open »EASY Starter«.
2.Connect to the inverter online
3.Modify desired parameters.
Conguring the network
EtherCAT
Parameter download
387