12.8 Lenze LECOM prole
For connecon to Lenze inverters with a LECOM control word (C135) and LECOM status word
(C150), the parameters listed in the following can be mapped to network registers.
Details
Mapping entries
•
LECOM control word (0x400B:002 (P592.02)): 0x400B0210
•
LECOM status word (0x400C:002 (P593.02)): 0x400C0210
•
Detailed informaon on the data mapping can be found in the chapter of the correspond-
ing network.
Parameter
Address Name / seng range / [default seng] Info
0x400B:002
(P592.02)
Process input data: LECOM control word
(Process data IN: LECOM ctrl word)
0x0000 ... [0x0000] ... 0xFFFF
Mappable control word with bit assignment in compliance with code
C135 of the 8200 Lenze inverter.
Bit 0 Acvate preset (bit 0)
Bit 1 Acvate preset (bit 1)
Bit 2 Reverse rotaonal direcon
Bit 3 Acvate quick stop
Bit 9 Disable inverter
Bit 10 Acvate user fault
Bit 11 Reset error (0-1 edge)
Bit 14 Acvate DC braking
0x400C:002
(P593.02)
Process output data: LECOM status word
(Process data OUT: LECOM stat. word)
•
Read only
Mappable status word with bit assignment in compliance with code
C150 of the 8200 Lenze inverter.
Bit 0 Acve parameter set (0 = set 1 or 3; 1 = set 2
or 4)
Bit 1 Power secon inhibited
Bit 2 Current or Torque limit reached
Bit 3 Frequency setpoint reached
Bit 4 Ramp generator (input = output)
Bit 5 Frequency < frequency threshold
Bit 6 Actual frequency = 0
Bit 7 Inverter disabled
Bit 8 Coded status bit 0
Bit 9 Coded status bit 1
Bit 10 Coded status bit 2
Bit 11 Coded status bit 3
Bit 12 Overtemperature warning
Bit 13 DC-bus overvoltage
Bit 14 Rotaonal direcon reversed
Bit 15 Ready for Operaon
Conguring the network
Lenze LECOM prole
342