9.3 Synchronous motor: Pole posion idencaon (PPI)
For controlling a permanent-magnet synchronous motor, the pole posion - the angle
between the motor phase U and the eld axis of the rotor - must be known.
•
For Lenze motors with absolute value encoder or resolver, the pole posion has already
been set correctly.
•
When incremental encoders are used (TTL or sin/cos encoders without absolute posion
informaon), a pole posion idencaon (PPI) is always required. This also applies to
Lenze motors.
Precondions
In 0x2C00 (P300.00) the motor control type "Sensorless control (SL PSM) [3]" is selected.
The "Pole posion idencaon (PPI) without movement" funcon is available for the iden-
caon of the pole posion for the inverter i5xx. ^ 167
9.3.1 Monitoring the pole posion idencaon
If an error occurs during the pole posion idencaon,
•
the procedure is stopped without the sengs being changed.
•
the response set in 0x2C60 is eected.
Parameter
Address Name / seng range / [default seng] Info
0x2C60 PPI monitoring: Reacon
•
From version 04.00
Selecon of the response triggered by the occurrence of an error during
the pole posion idencaon (PLI).
Associated error code:
•
28961 | 0x7121 - Pole posion idencaon fault
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
9.3.2 Pole posion idencaon (PPI) without movement
The PLI funcon can also be used if no motor revoluon is possible (holding brake acve).
NOTICE
With an incorrect parameter seng and dimensioning of the inverter, the maximum permissi-
ble motor current may be exceeded during the pole posion idencaon.
Possible consequence: irreversible damage of the motor.
▶
Set the motor data correctly. 4Motor data ^ 50
▶
Only use an inverter that is performance-matched to the motor.
Precondions
•
The wiring of the three motor phases and the motor encoder must be carried out accord-
ing to the specicaons from the mounng instrucons.
•
The inverter is ready for operaon (no fault acve).
•
For pole posion idencaon (PPI) without movement, the motor must be at standsll.
Parameter
Address Name / seng range / [default seng] Info
0x2C63:001 PPI without movement: Execuon
•
Seng can only be changed if the inverter is inhibi-
ted.
•
From version 04.00
Starng performance (with or without pole posion idencaon before
the start).
0 Deacvated No pole posion is idened.
2 Aer each enable Aer every inverter release, the pole posion is idened without any
movement.
Conguring the feedback system
Synchronous motor: Pole posion idencaon (PPI)
Pole posion idencaon (PPI) without movement
167