12.2.1 Opon 1: Dene network as standard setpoint source
If the setpoint is to be specied exclusively via the network, the network for the correspond-
ing control can be simply set as the standard setpoint source.
Seng for the frequency control: 0x2860:001 (P201.01) = "Network [5]".
See the following table for sengs for addional controls.
Control: size Parameter Seng Further informaon
Frequency control: frequency set-
point
0x2860:001
(P201.01)
Network [5]
Frequency control 4Standard setpoint source ^ 82
PID control: reference value 0x2860:002
(P201.02)
Network [5]
Frequency control 4Conguring the process controller ^ 116
PID control: feedback of the control
variable (actual value)
0x4020:002
(P600.02)
Network [5]
PID control: speed feedforward
control
0x4020:004
(P600.04)
Network [8]
Torque control: torque setpoint 0x2860:003
(P201.03)
Network [5]
Torque control4Standard setpoint source ^ 151
Conguring the network
Dene setpoint via network
Opon 1: Dene network as standard setpoint source
297