10.6.2.4 Migraon of Lenze Inverter Drives 8200/8400
The behaviour of the Lenze Inverter Drives 8200/8400 in case of automac DC braking is dif-
ferent: In case of these inverters, aer the auto DCB hold me has elapsed, the motor is dee-
nergised (by means of pulse inhibit) unl the setpoint exceeds the auto DCB operang thresh-
old. In order to make a migraon to the i500 inverter series easier, the seng 0x2B84:006
(P704.06) = "1" serves to acvate the same behaviour in the i500.
The following example illustrates the behaviour of the funcon if 0x2B84:006 (P704.06) = "1".
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:013 (P400.13) Reverse rotaonal direcon Digital input 3 [13]
0x2838:003 (P203.03) Stop method Standard ramp [1]
0x2B84:001 (P704.01) Current 50 %
0x2B84:002 (P704.02) Automac hold me 10 s
0x2B84:003 (P704.03) Automac operang threshold 10 Hz
0x2B84:006 (P704.06) DC brake with inverter disable 1
t
t
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
-40 Hz
-60 Hz
-50 Hz
-30 Hz
-20 Hz
-10 Hz
t
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
t
t
t
t
t
0x2DDD
DC brake
DC brake
Stop active [53]
DC braking active [67]
Running [50]
Power section switched-on
Digital input 3 [13] Reversal rotation direction
Output frequency
Output signals
Output trigger
Digital input 1 [11] Run
Constant TRUE [1] Enable inverter
Input signals
Frequency setpoint selection
FunctionTrigger
The status signals can be assigned to digital outputs. 4Congure digital outputs ^ 263
If the setpoint falls below the operang threshold set in 0x2B84:003 (P704.03), the DC braking gets acve for the hold me set in
0x2B84:002 (P704.02).
Aer the hold me has elapsed, the power secon is switched o.
If the setpoint exceeds the operang threshold again, the power secon is switched on again. The motor is accelerated to the setpoint
again.
Conguring the motor control
Parameterisable motor funcons
DC braking
202