EasyManua.ls Logo

Lenze i550

Lenze i550
704 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.5 Change over to ramp 2 during operaon
Two dierent ramps can be parameterised for the frequency setpoint. The change-over to the
ramp 2 can be iniated manually or automacally.
Details
For ramp 2, the acceleraon me 2 set in 0x2919 (P222.00) and the deceleraon me 2 set in
0x291A (P223.00) apply.
The change-over to ramp 2 is eected automacally if the frequency setpoint (absolute value)
≥ auto-changeover threshold 0x291B (P224.00).
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
0x2919
0x2917
0x291A
0x2918
0x291B = 20 Hz
0x2DDD
Ramp 2 active
Ramp 1 active
Output signals
Output frequency
Input signals
Frequency setpoint selection
The "Acvate ramp 2" 0x2631:039 (P400.39) funcon serves to manually acvate the acceler-
aon me 2 and the deceleraon me 2 .
Parameter
Address Name / seng range / [default seng] Info
0x2919
(P222.00)
Acceleraon me 2
(Accelerat.me 2)
0.0 ... [5.0] ... 3600.0 s
Acceleraon me 2 for the operang mode "MS: Velocity mode".
The acceleraon me set refers to the acceleraon from standsll to
the maximum frequency set. In the case of a lower setpoint selecon,
the actual acceleraon me is reduced accordingly.
The acceleraon me 2 is acve if the frequency setpoint (absolute
value) ≥ auto switching threshold 0x291B (P224.00) or the trigger
assigned to the funcon "Acvate ramp 2" in 0x2631:039 (P400.39) =
TRUE.
The acceleraon me 2 is also used for changing the MOP setpoint
generated by the "motor potenometer" funcon.
Seng is not eecve in the operang mode 0x6060 (P301.00) =
"CiA: Velocity mode [2]".
0x291A
(P223.00)
Deceleraon me 2
(Decelerat.me 2)
0.0 ... [5.0] ... 3600.0 s
Deceleraon me 2 for the operang mode "MS: Velocity mode".
The deceleraon me set refers to the deceleraon from the maxi-
mum frequency set to standsll. In the case of a lower actual fre-
quency, the actual deceleraon me is reduced accordingly.
The deceleraon me 2 is acve if the frequency setpoint (absolute
value) ≥ auto change-over threshold 0x291B (P224.00) or the trigger
assigned to the funcon "Acvate ramp 2" in 0x2631:039 (P400.39) =
TRUE.
The deceleraon me 2 is also used for changing the MOP setpoint
generated by the "motor potenometer" funcon.
Seng is not eecve in the operang mode 0x6060 (P301.00) =
"CiA: Velocity mode [2]".
0x291B
(P224.00)
Auto-changeover threshold of ramp 2
(Ramp 2 thresh.)
0.0 ... [0.0] ... 599.0 Hz
Threshold for the automac change-over to acceleraon me 2 and
deceleraon me 2.
The change-over is eected if the frequency setpoint (absolute value)
≥ auto change-over threshold.
With the seng 0, the automac change-over funcon is deacvated.
Conguring the frequency control
Change over to ramp 2 during operaon
143

Table of Contents

Other manuals for Lenze i550

Related product manuals