14.4 Posion counter
This funcon counts the number of motor revoluons. The current counter content (actual
posion) can be output as process data value via network to implement a simple posion con-
trol in a higher-level Controller.
PLC
positioning
PLC
positioning
PLC
positioning
ixxxixxxixxx
Tacho-
meter
Tacho-
meter
MotorMotorMotor
Mech
Count valueCount valueCount value
Setpoint frequencySetpoint frequencySetpoint frequency
Precondions
An HTL encoder must be connected to and set at the digital inputs DI3/DI4. 4HTL
encoder ^ 162
As an alternave, the number of motor revoluons from the motor model can be recon-
structed. For this purpose, the motor control type "Sensorless control (SL PSM) [3]" must
be selected and set in 0x2C00 (P300.00). 4Sensorless control for synchronous motor (SL-
PSM) ^ 170
The
posion control must be implemented in the Controller.
Details
The signal source for the posion counter is selected in 0x2C49:001 (P711.01). The posion
counter can count forwards and backwards. The current counter content (actual posion) is
displayed in 0x2C49:003 (P711.03). Aer the maximum or minimum value has been reached,
an overow takes place.
Reset posion counter:
The posion counter is reset when the supply voltage is switched on.
The posion counter can be reset manually via the "Posion counter reset" 0x2631:054
(P400.54) funcon or the NetWordIN1 0x4008:001 (P590.01) data word. For a reset via
NetWordIN1, the "Posion counter reset [54]" funcon must be assigned to a bit of the
data word. Depending on the selecon in 0x2C49:002 (P711.02), the reset can be made
either edge-controlled or status-controlled.
Parameter
Address Name / seng range / [default seng] Info
0x2631:054
(P400.54)
Funcon list: Posion counter reset
(Funcon list: PosCounter reset)
From version 03.00
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Posion counter reset" funcon.
Trigger = FALSE-TRUE edge: Reset posion counter manually.
Trigger = FALSE: no acon.
Notes:
In 0x2C49:002 (P711.02) it can be selected whether the reset is to be
eected edge-controlled (default seng) or status-controlled.
0 Not connected No trigger assigned (trigger is constantly FALSE).
Addional funcons
Posion counter
538