Assignment of the user data depending on the data type
Depending on the data type used, the user data is assigned as follows:
Data type Length User data assignment
Byte 1 Byte 2 Byte 3 Byte 4 Byte ...
String x bytes Data (x bytes)
U8 1 byte Data 0x00
U16 2 bytes HIGH byte LOW byte
Data Data
U32 4 bytes HIGH word LOW word
HIGH byte LOW byte HIGH byte LOW byte
Data Data Data Data
12.16.5 Monitoring
The parameters for seng network monitoring funcons are described below.
Parameter
Address Name / seng range / [default seng] Info
0x2859:001
(P515.01)
PROFINET monitoring: Watchdog elapsed
(PROFINET monit.: WD elapsed)
•
From version 02.00
Selecon of the response to a permanent interrupon of the communi-
caon to the IO controller.
Corresponding error code: 33168 | 0x8190 "PROFINET: Watchdog me-
out"
Associated error code:
•
33168 | 0x8190 - Network: watchdog meout
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:002
(P515.02)
PROFINET monitoring: Data exchange exited
(PROFINET monit.: Data exch.exited)
Selecon of the response to exing the "Data Exchange" state.
Corresponding error code: 33171 | 0x8191 "PROFINET: Exit Data
Exchange"
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:003
(P515.03)
PROFINET monitoring: Invalid conguraon
(PROFINET monit.: Invalid cong)
•
From version 02.00
Selecon of the response triggered by the recepon of invalid congura-
on data.
Corresponding error code: 33414 | 0x8286 "PROFINET: Conguraon
error"
Associated error code:
•
33414 | 0x8286 - Network: PDO mapping error
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:004
(P515.04)
PROFINET monitoring: Inialisaon error
(PROFINET monit.: Init. error)
•
From version 02.00
Selecon of the response triggered by the occurrence of an error during
the inialisaon of the network component.
Corresponding error code: 33170 | 0x8192 "PROFINET: Inialisaon
error"
Associated error code:
•
33170 | 0x8192 - Network: inialisaon error
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
Conguring the network
PROFINET
Parameter data transfer
491