33169 0x8191 Network: disrupon of cyclic data exchange Keypad display: Cycl data error
Cause Error type/response Remedy
The communicaon partner has interrupted the
cyclic data exchange.
No response (Congurable)
•
Check wiring of the network.
•
The slave must receive new parameterisaon
and conguraon les by the master, in
order to be able to exchange data again.
Seng parameters: 0x2859:002 (P515.02)
33170 0x8192 Network: inialisaon error Keypad display: Net. Init. error
Cause Error type/response Remedy
The inialisaon of the communicaon stack
has been interrupted due to an incorrect
address seng or communicaon congura-
on.
Trouble (Congurable) Check master/slave conguraon and restart
the devices.
Seng parameters:
0x2859:004 (P515.04) (PROFIBUS)
0x2859:004 (P515.04) (EtherCAT)
0x2859:004 (P515.04) (EtherNet/IP)
0x2859:004 (P515.04) (PROFINET)
0x2859:004 (P515.04) (Modbus TCP)
33171 0x8193 Network: invalid cyclic process data Keypad display: Inv. cyclic data
Cause Error type/response Remedy
The cyclic process data received are invalid. Trouble (Congurable) Check cyclic process data sent by the master.
Seng parameters:
0x2859:005 (P515.05) (PROFIBUS)
0x2859:005 (P515.05) (EtherCAT)
0x2859:005 (P515.05) (EtherNet/IP)
0x2859:005 (P515.05) (PROFINET)
33185 0x81A1 Modbus: network me-out Keypad display: Modbus me-out
Cause Error type/response Remedy
No valid messages have been received via the
Modbus for a longer me than the me-out
me set in 0x2858:002 (P515.02).
Fault (Congurable)
•
Check communicaon with the master.
•
Check wiring.
•
Check bus terminaon.
Seng parameters: 0x2858:001 (P515.01)
33186 0x81A2 Modbus: incorrect request by master Keypad display: Modbus request
Cause Error type/response Remedy
The request by the master is invalid, e. g. invalid
CRC checksum, non-supported funcon code,
or impermissible data access.
Warning
•
The inverter (slave) responds to the master
with an error code:
0x01 = invalid funcon code
0x02 = invalid data address
0x03 = invalid data value
0x04 = slave device failure
Check request by the master:
•
Value in the valid range?
•
Funcon code valid?
•
No impermissible write access? (e. g. with
regard to read-only parameters)
33200 0x81B0 Network communicaon faulty Keypad display: Comm. faulty
Cause Error type/response Remedy
In case of the Ethernet communicaon inter-
face, an internal soware error has occurred.
Trouble
•
Switch inverter o and on again.
•
In the event of a power failure during a rm-
ware download, it is required to reload the
rmware via the USB module and then
restart the inverter.