Address Name / seng range / [default seng] Info
0x4018:006 Relay: Trigger signal state
Read only
Display of the logic state of the trigger signal for the relay (without tak-
ing a ON/OFF delay set and inversion into consideraon).
0 FALSE
1 TRUE
Related topics
4Congure digital inputs ^ 243
4Congure digital outputs ^ 263
17.4.3.2 Analog inputs and outputs
The following parameters serve to diagnose the analog inputs and outputs of the inverter.
Parameter
Address Name / seng range / [default seng] Info
0x2DA4:001
(P110.01)
Diagnoscs of analog input 1: Value in percent
(AI1 diagnoscs: AI1 terminal %)
Read only: x.x %
Display of the current input value at X3/AI1 scaled as value in percent.
100 % ≡ 10 V or 20 mA or 5 V
0x2DA4:002
(P110.02)
Diagnoscs of analog input 1: Frequency value
(AI1 diagnoscs: AI1 scaled freq.)
Read only: x.x Hz
Display of the current input value at X3/AI1 scaled as a frequency value.
The standard setpoint source for operang mode 0x6060 (P301.00) =
"MS: Velocity mode [-2]" is selected in 0x2860:001 (P201.01).
0x2DA4:003
(P110.03)
Diagnoscs of analog input 1: Process controller value
(AI1 diagnoscs: AI1 scaled PID)
Read only: x.xx PID unit
Display of the current input value at X3/AI1 scaled as a process controller
value.
The standard setpoint source for the reference value of PID control is
selected in 0x2860:002 (P201.02).
0x2DA4:004
(P110.04)
Diagnoscs of analog input 1: Torque value
(AI1 diagnoscs: AI1 scaled torq.)
Read only: x.x %
Display of the current input value at X3/AI1 scaled as a percentage tor-
que value.
100 % ≡ permissible maximum torque 0x6072 (P326.00)
The standard setpoint source for operang mode 0x6060 (P301.00) =
"MS: Torque mode [-1]" is selected in 0x2860:003 (P201.03).
0x2DA4:016
(P110.16)
Diagnoscs of analog input 1: Status
(AI1 diagnoscs: AI1 status)
Read only
From version 04.00
Bit coded display of the status of analog input 1 (X3/AI1).
Bit 0 Mode 0: 0 ... 10 VDC acve
Bit 1 Mode 1: 0 ... 5 VDC acve
Bit 2 Mode 2: 2 ... 10 VDC acve
Bit 3 Mode 3: -10 ... 10 VDC acve
Bit 4 Mode 4: 4 ... 20 mA acve
Bit 5 Mode 5: 0 ... 20 mA acve
Bit 6 24 V supply OK
Bit 7 Calibraon successful
Bit 8 Monitoring threshold exceeded/not reached
Bit 9 Input current too low (mode 4)
Bit 10 Input voltage too low (mode 2)
Bit 11 Input voltage too high (mode 4)
0x2DA5:001
(P111.01)
Diagnoscs of analog input 2: Value in percent
(AI2 diagnoscs: AI2 terminal %)
Read only: x.x %
Display of the current input value at X3/AI2 scaled as a value in percent.
100 % ≡ 10 V or 20 mA or 5 V
0x2DA5:002
(P111.02)
Diagnoscs of analog input 2: Frequency value
(AI2 diagnoscs: AI2 scaled freq.)
Read only: x.x Hz
Display of the current input value at X3/AI2 scaled as a frequency value.
The standard setpoint source for operang mode 0x6060 (P301.00) =
"MS: Velocity mode [-2]" is selected in 0x2860:001 (P201.01).
0x2DA5:003
(P111.03)
Diagnoscs of analog input 2: Process controller value
(AI2 diagnoscs: AI2 scaled PID)
Read only: x.xx PID unit
Display of the current input value at X3/AI2 scaled as a process controller
value.
The standard setpoint source for the reference value of PID control is
selected in 0x2860:002 (P201.02).
0x2DA5:004
(P111.04)
Diagnoscs of analog input 2: Torque value
(AI2 diagnoscs: AI2 scaled torq.)
Read only: x.x %
Display of the current input value at X3/AI2 scaled as a percentage tor-
que value.
100 % ≡ permissible maximum torque 0x6072 (P326.00)
Diagnoscs and fault eliminaon
Diagnosc parameters
I/O diagnoscs