6.4 Changing the control source during operaon
The term "control sources" in this connecon refers to the digital signal sources from which
the inverter receives its start, stop, and reversal commands.
Possible control sources:
Digital inputs
Keypad
Network
Details
First, select in 0x2824 (P200.00) whether the start of the motor is to be congured exibly
(default seng) or exclusively via the keypad. 4Control selecon^ 54
If "Flexible I/O conguraon" is set, a change-over from one control source to another can be
eected during operaon via the funcons listed in the following table. The inverter not only
supports such a change-over via its digital inputs, but also as a funcon of internal inverter
states.
Acvate keypad control
0x2631:012 (P400.12)
Acvate network control
0x2631:037 (P400.37)
Acve control source
FALSE / Not connected FALSE / Not connected
Flexible I/O conguraon (default seng)
The motor is controlled via the digital inputs.
For precongured assignment of the digital inputs, see chapter "Func-
on assignment of the inputs and outputs (default seng)". ^ 48
For descripon of the basic funcons for controlling the motor, see
chapter "Flexible I/O conguraon of the start, stop and rotang
direcon commands". ^ 59
FALSE / Not connected TRUE
Network
Starng the motor is only possible via the network control word.
Excepon: jog operaon; see chapter "Flexible I/O conguraon of
the start, stop and rotang direcon commands". ^ 59
4Example: Change-over from terminal control to network control^ 81
TRUE Any
Keypad
Starng the motor is only possible via the keypad key.
Excepon: jog operaon; see chapter "Flexible I/O conguraon of
the start, stop and rotang direcon commands". ^ 59
4Example: Change-over from terminal control to keypad control^ 79
Parameter
Address Name / seng range / [default seng] Info
0x2631:012
(P400.12)
Funcon list: Acvate keypad control
(Funcon list: Keypad control)
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Acvate keypad control" funcon.
Trigger = TRUE: acvate keypad as control source.
Trigger = FALSE: no acon / deacvate keypad as control source again.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:037
(P400.37)
Funcon list: Acvate network control
(Funcon list: Network control)
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Acvate network control" funcon.
Trigger = TRUE: Acvate network control.
Trigger = FALSE: no acon / deacvate network control again.
0 Not connected No trigger assigned (trigger is constantly FALSE).
114 Network control acve (from version 02.00) TRUE if the network control is requested via bit 5 of the AC drive control
word 0x400B:001 (P592.01). Otherwise FALSE.
Notes:
Set this selecon if the network control is to be acvated via bit 5 of
the AC drive control word.
The AC drive control word can be used with any communicaon pro-
tocol.
4AC drive control word ^ 328
Start, stop and rotang direcon commands
Changing the control source during operaon
77