6.4 Changing the control source during operaon
The term "control sources" in this connecon refers to the digital signal sources from which
the inverter receives its start, stop, and reversal commands.
Possible control sources:
•
Digital inputs
•
Keypad
•
Network
Details
First, select in 0x2824 (P200.00) whether the start of the motor is to be congured exibly
(default seng) or exclusively via the keypad. 4Control selecon^ 54
If "Flexible I/O conguraon" is set, a change-over from one control source to another can be
eected during operaon via the funcons listed in the following table. The inverter not only
supports such a change-over via its digital inputs, but also as a funcon of internal inverter
states.
Acvate keypad control
0x2631:012 (P400.12)
Acvate network control
0x2631:037 (P400.37)
Acve control source
FALSE / Not connected FALSE / Not connected
Flexible I/O conguraon (default seng)
•
The motor is controlled via the digital inputs.
•
For precongured assignment of the digital inputs, see chapter "Func-
on assignment of the inputs and outputs (default seng)". ^ 48
•
For descripon of the basic funcons for controlling the motor, see
chapter "Flexible I/O conguraon of the start, stop and rotang
direcon commands". ^ 59
FALSE / Not connected TRUE
Network
•
Starng the motor is only possible via the network control word.
•
Excepon: jog operaon; see chapter "Flexible I/O conguraon of
the start, stop and rotang direcon commands". ^ 59
4Example: Change-over from terminal control to network control^ 81
TRUE Any
Keypad
•
Starng the motor is only possible via the keypad key.
•
Excepon: jog operaon; see chapter "Flexible I/O conguraon of
the start, stop and rotang direcon commands". ^ 59
4Example: Change-over from terminal control to keypad control^ 79
Parameter
Address Name / seng range / [default seng] Info
0x2631:012
(P400.12)
Funcon list: Acvate keypad control
(Funcon list: Keypad control)
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Acvate keypad control" funcon.
Trigger = TRUE: acvate keypad as control source.
Trigger = FALSE: no acon / deacvate keypad as control source again.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:037
(P400.37)
Funcon list: Acvate network control
(Funcon list: Network control)
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Acvate network control" funcon.
Trigger = TRUE: Acvate network control.
Trigger = FALSE: no acon / deacvate network control again.
0 Not connected No trigger assigned (trigger is constantly FALSE).
114 Network control acve (from version 02.00) TRUE if the network control is requested via bit 5 of the AC drive control
word 0x400B:001 (P592.01). Otherwise FALSE.
Notes:
•
Set this selecon if the network control is to be acvated via bit 5 of
the AC drive control word.
•
The AC drive control word can be used with any communicaon pro-
tocol.
4AC drive control word ^ 328
Start, stop and rotang direcon commands
Changing the control source during operaon
77